GB
50
2.1 Technical data and operating limits
2 TECHNICAL INFORMATION
Water heater model: tank (ECO HYDRO KIT)
combined with Heat Pump (MIRAI-SMI)
u.m.
ITM-200 B
EH0618DC
ITM-200 B
EH1018DC
ITM-200 B
EH1218DC
Data according the regulation UE N. 812-814/2013
Declared load profile
L
L
XL
Energy efficiency class
A
A
A
Annual electricity consumption AEC
kWh
1023
1006
1582
Sound power level L
WA
outdoor
dB(A)
60
63
62
Data according the standard EN 16147. Average climatic conditions: outdoor air BS 7(6) °C, indoor air 20 °C
Thermostat temperature setting (∆t)
°C
50 - 8
50 - 8
50 - 8
Heating up time (
1
)
h:min
1:45
1:20
1:00
Heating up energy input (
1
)
kWh
2,65
2,61
2,74
Standby power input
W
40
43
44
COP
DHW
(
2
)
2,40
2,40
2,55
Maximum volume of usable hot water (40 °C)
ℓ
210
210
210
Reference hot water temperature
°C
49,7
49,7
49,7
Rated heat output P
rated
kW
4,2
5,6
7,3
Hot water tank model (ECO HYDRO KIT) ITM-200 B
Data according the regulation UE N. 812-814/2013 and the standard EN 12897:2020
Energy efficiency class
C
Standing loss S
W
80
Nominal (usable) volume of storage V
ℓ
180
Nominal volume heat exchanger
ℓ
12
Max working pressure
bar
6
Test pressure
bar
9
Maximum safety temperature
°C
95
Inertial storage technical characteristics
Total capacity inertial storage (usable volume)
ℓ
26
Max working pressure (
5
)
bar
3
Test pressure
bar
6
Standing loss S (
4
)
W
40
Other data
Power supply
230V~ 50Hz
Electrical power DHW integrative resistance
kW
1,20
Maximum power consumption
kW
3,75
5,15
5,85
Maximum current consumption
A
16,6
22,9
28,4
IP Grade of protection
IPX1B
Sound pressure level outdoor (
3
)
dB(A)
38
41
40
Dimensions
Dimensions (LxDxH)
mm
601 x 639 x 1973
Weight (without water)
kg
165
Working range
Indoor temperature
°C
0 ÷ 40
Water temperature
°C
5 ÷ 60
(
1
) Heating up of the tank from 10 °C to the thermostat temperature
(
2
) COP calculated following the water draw-offs of the load profile
(
3
) Value referred to directionality factor equal to 2 in open field and distance from the unit equal to 5 m
(
4
) In compliance with UNI EN 12897 with T
water
= 65 °C and T
ambient
= 20 °C
(
5
) If the buffer tank is NOT connected to the MIRAI-SMI heat pump, a safety valve 2,5 bar must be installed to overpressure protection
Summary of Contents for ECO HYDRO KIT ITM-200 B
Page 1: ...ECO HYDRO KIT ITM 200 B MANUALE INSTALLAZIONE ED USO INSTALLATION AND USE MANUAL Rev B 04 2021...
Page 14: ...IT 14 Esempio di installazione 1 Eco Hydro kit ITM 200 B 2 Pompa di calore MIRAI SMI...
Page 43: ......
Page 56: ...GB 56 Installation example 1 Eco Hydro kit ITM 200 B 2 MIRAI SMI heat pump...
Page 78: ...GB 78...