MTEC.DXi.H/DXi.HF.GB-3 Use and Maintenance technical manual DXi.H/DXi.HF English
Emibyte DXi.H/DXi.HF
Direct expansion close control
18. Probe alarm
a. The corresponding probe is defective or
disconnected
Check the probe connection and its opera-
tion, if necessary replace it
19. The fan does not start
a. Current interruption / black out
Check the main switch and the power cable
b. Protection switch open
Reset the protection switch ad check the
motor current and absorption
c. Transformer protection activated
Check for any auxiliary short-circuit
d. Contactor defective
Repair or replace the contactor
e. The fans are not powered
Check the fans electric power supply
f. The fan thermal protection block its
operation
Check if the rotori s locked or if the power
VXSSO\LVLQVXI¿FLHQWRULIWKHUHDSKDVHORVV
g. Controller not powered (display OFF)
Check for any auxiliary short-circuit
h. Unit switched off (OFF position)
Turn ON on the keyboard