MTEC.DXi.H/DXi.HF.GB-3 Use and Maintenance technical manual DXi.H/DXi.HF English
Emibyte DXi.H/DXi.HF
Direct expansion close control
Info - Freecool. Z014
Damper/valve on: []
Freec.temp.: 23.1
°
C
Freec.request: 0.0%
Shown when the FREECOOLING function is activated.
Info - Hot Req. Z016
Request hot valve:
0%
Request heaters:
81%
It allows to consult the information on the heating mode.
Info - Heater. Z018
Heater 1 : []
Heater 2 : []
It allows you to check whether the digital outputs of the heaters are active.
Info - Heater. Z019
16:32 FRI 29/03/2019
Sched. is not running
View only screen; it allows you to check some operating data of the unit.
Info - Fan Z020
Curr.speed: 700rpm
Curr.request: 0%
Min speed: 40.0%
Max speed: 70.0%
Power out: 4.0W
Drive temp.: 40.0
°
C
Provides information on operating fans. Possibility to choose which ones to activate from the
E008 mask.
Info - Fan2 Z024
Curr.speed: 0rpm
Curr.request: 0%
Min speed: 40.0%
Max speed: 70.0%
Power out: 4.0W
Drive temp.: 40.0
°
C
Provides information on operating fans. Possibility to choose which ones to activate from the
E028 mask.
Unit Conf. Z101
Return temperature
(U01)
Value: 24.2
°
C
Offset: 0.0
°
C
Type: NTC
Provides information on the input temperature of the machine.
Unit Conf. Z102
Supply temperature
(U02)
Value: 23.2
°
C
Offset: 0.0
°
C
Type: NTC
Provides information on the output temperature of the machine.
Unit Conf. Z103
Return humidity
(U04)
Value: 48.4%
Offset: 0.0%
Type: 0-10V
Mimum: 10.0%
Maximum: 90.0%
Provides information on the input humidity value of the machine. It can be enabled by the
Ga10 mask.
Unit Conf. Z105
Freecool. temperature
(U06)
Value: 23.1
°
C
Offset: 0.0
°
C
Type: NTC
Provides information on freecooling settings. It can be enabled by the Ga07 mask.
Unit Conf. Z106
Fan diff. press.
(U05)
Value: 7166.9 m3/h
Mimum: 0.0 m3/h
Maximum: 7589.5 m3/h
Provides information on the differential pressure level of the fans. It can be enabled by the
Ga10 mask.
Unit Conf. Z121
External temperature
for compensation
(U07)
Value: 20.8
°
C
Offset: 0.0
°
C
Type: NTC
Provides information on temperature set point compensation settings.