![Emicon EMIBYTE DXi.H Use And Maintenance Download Page 68](http://html1.mh-extra.com/html/emicon/emibyte-dxi-h/emibyte-dxi-h_use-and-maintenance_2401334068.webp)
Rev. 3 02-2021
68
Main Menu
1/5
Language
Network
Date/Time
Main Menu
9/10
H. Alarm logs
I. Others setting
G. Unit setting
Main Menu
8/10
H. Alarm logs
L. Logout
I. Other settings
MTEC.DXi.H/DXi.HF.GB-3 Use and Maintenance technical manual DXi.H/DXi.HF English
Emibyte DXi.H/DXi.HF
Direct expansion close control
Unit regulation Gb48
Temperature and
humidity alarm
Delay time: 600s
High and low humidity or temperature delay alarm displaying / settings.
Unit regulation Gb49
overload fan
Delay time: 10s
Main fans thermal alarm delay displaying / settings.
Unit regulation Gb50
Number alarm/hour
LP: 3
HP/Overload Comp.: 1
High or low pressure alarm delay number (per hour) displaying / settings.
Unit regulation Gb51
Number alarm/hour
Overload Heater: 3
Heaters thermal alarm delay number (per hour) displaying / settings.
Unit regulation Gb56
Disable Ti: [
я
]
Possibility to set integral time = 0 or not.
Unit regulation Gb57
En.Reg.Flow: [
я
]
$LUÀRZUHJXODWLRQHQDEOLQJ
0HQX2WKHUVHWWLQJV
'DWD7LPH
Date/Time change IA01
Format: DD/MM/YY
Date: 05/04/19
Hour: 10:52:02
Day: Friday
Date and hour format settings.
Timezone IA02
Current timezone:
GMT
Change to:
GMT
Update Timezone: NO
Time zone activation.