Main Menu
6/10
E. Ventilation
F. CPY
G. Unit settings
MTEC.DXi.H/DXi.HF.GB-3 Use and Maintenance technical manual DXi.H/DXi.HF English
Emibyte DXi.H/DXi.HF
Direct expansion close control
It will be possible the visualization of some masks referred to the fans and their parameters.
Supply fan E001
Type: EC
Min speed(%) : 40.0%
Max speed(%) : 70.0%
Manual/Dehum.speed:
20.0%
'LVSOD\LQJWKHIDQVVSHHGPLQHPD[DQGWKHGHKXPLGL¿FDWLRQPRGH
Supply fan E002
Limit speed
Min speed(%) : 20.0%
Time startup : 60 s
Time shutdown : 30 s
During the switch ON and OFF the fans are maintened to a constant speed for a settable
time; in this masks is possible to visualize the set time.
Supply fan E008
Fan enabled : [
я
]
Num.of fans: 2
Fan 1 online : [ ]
Fan 1 online : [ ]
Displaying the enabled fans, it is possible to enable to 4 fans in serial mode.
CPY F001
CPY
Enable: []
Only if the humidity
probe is enabled
$OORZVWKHYLVXDOL]DWLRQWRFKHFNLIWKHKXPLGL¿HUPDQDJHPHQWFDUGLVHQDEOHG
0HQX&3<
To enter in CPY menu press
,key, then
and
to select the F.CPY menu and press
WRFRQ¿UP