5.The Concrete Explanation of Function Parameters
EM8 User's Manual
67
Diagram 5-29: Single cycle and stop (mode 5)
Parameters of the running curve in diagram 5-28 and 5-29 are set as: [C-14]= 3, keep last step mode
[C-27]= 0, [C-33 ]= 0, running time for step 5 and step 7 is 0, so these two steps are skipped in the curve.
Diagram 5-30: Swing frequency running (mode 4)
Code
Name
Description
Factory setting
C-36
Jump frequency 1
0.00~Upper-limit frequency
0.00
C-37
Amplitude of jump
frequency 1
0.00 ~5.00Hz
0.00
C-38
Jump frequency 2
0.00~Upper-limit frequency
0.00
C-39
Amplitude of jump
frequency 2
0.00 ~5.00Hz
0.00
C-40
Jump frequency 3
0.00~Upper-limit frequency
0.00
C-41
Amplitude of jump
frequency 3
0.00 ~5.00Hz
0.00
While mechanical resonance may happen at a certain frequency on the load connected to the inverter, you
can avoid it with jump frequency.
You can choose from 3 kinds of jump frequency. If this parameter is set to 0, jump frequency function is
invalid.