2.Installation and Wiring
EM8 User's Manual
5
Model No.
Voltage
Power
Current
G.W
Inverter size
EM8-G3-350
EM8-P3-400
380
350
640
450
1828/981/496
EM8-G3-400
EM8-P3-500
380
400
690
EM8-G3-500
EM8-P3-630
380
500
860
EM8-G3-630
--
380
630
1100
2.2 Specification
Items
Specification
Input
Rated voltage and frequency
Single phase 220/Three Phase 380V, 50/60Hz
Voltage allowable deviation range 200V~240V,320V~460V
Output
Voltage
0~380V
Frequency
0Hz~500Hz
Over-load capability
G3 Series:
150% rated current for 1 minute
180% rated current for 2seconds
P3 Series:
120% rated current for 1 minute
150% rated current for 2seconds
Control
character
Control mode
V/F Control
Frequency
setting
resolution
Analog terminal input 0.1% of max output frequency
Digital setting
0.01Hz
Panel analog setting
0.4 % of max frequency
External pulse
0.1% of max frequency
Frequency
accuracy
Analog Input
Within ±0.2% of max. output frequency
Digital Input
Within ±0.01% of setting output frequency
External pulse
Within ±0.1% of max. output frequency
V/F curve
(Voltage-frequency character)
Base frequency can be set from 5~500Hz arbitrarily,
and there are three kinds of curve: constant
torque ,Dec torque 1 and Dec torque 2.
Torque boost
Manual Setting: 0~20% of rated output, Auto-boost:
Automatically boost torque according to output
current.
Auto energy-saving running
Adjust output voltage and slip compensation properly
according to output current, which will make the
motor working in highest efficiency.
Acc./Dec time setting
0.1~6000seconds can be set continuously, and S type
and line type can be selected.
Braking
Dynamic braking
Over 75% (External braking resistor)
DC braking
It is selected respectively at start and stop, and its
frequency is 0~15Hz, the action voltage is 0~15%, and
the action time is 0~20.0 second or act continuously.
Auto current-limiting function
Fast auto current-limiting function ensures not to occur
the over-current during the accelerate process or under
the impact load.