4.Function Parameter List
EM8 User's Manual
31
Code
Name
Description
Min.
unit
Factory
setting
Change
Code
addr.
C-67
Wake up threshold
value
0.001~[C-68]
0.001 0.000
9FH
C-68
Sleep threshold value [C-67]~[C-62]
0.001 1.000
A0H
C-69
Pump switch time
0.1s~1000s
0.1
300.0
A1H
C-70
Electromagnetic
switch delay time
0.1~10.0h
0.1
0.5
×
A2H
C-71
Multi-pump running
mode
0: Switch as the fixed sequence
1: Timing alternation run
1
0
A3H
C-72
Timing alter interval
0.5~100.0h
0.1
5.0
A4H
C-73
Timing water-supply 0.5~24.0h
0.1
24.0
A5H
C-74
AM output hardware
calibration factor
95.0~104.5%
0.1
100%
A6H
C-75
AO output hardware
calibration factor
95.0~104.5%
0.1
100%
A7H
C-76
Suppress swing of
analog input
0~30
1
3
A8H
C-77
Braking unit usage
0~100
1
25
A9H
C-78
Inverter address
0~30
1
0
×
AAH
C-79
Data format
0: No parity check
1: Even parity check
2: Odd parity check
1
0
×
ABH
C-80
Baud rate
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
1
3
×
ACH
C-81
Master inverter
setting
0: The inverter is slave
1: The inverter is master
1
0
×
ADH
C-82
Linkage run setting
ratio
0.10~10.00
0.01
1.00
AEH
C-83
RS485 communication
wire-break action
mode
0: Stop
1: Keep the existing state
1
0
AFH
C-84
Panel potentiometer
gain factor
0.01~5.00
0.01
1.00
B0H
4.4 State monitor parameter list
Monitor code
Content
Unit
Address of code
d-0
Present output frequency of inverter
0.01Hz
D8H
d-1
Present output current of inverter
0.1A
DCH
d-2
Present output volt of inverter
1V
DDH
d-3
Motor’s current speed
1Rpm
DEH