Chapter 4  Operation Instructions      35 

SmartCabinet Integrated Solution    User Manual 

Chapter 4   Operation Instructions 

This chapter introduces the operation instructions of SmartCabinet, including check before startup, and procedures of 
power on and power off. 

4.1   Check Before Startup 

Check the following before startup of SmartCabinet: 

1. Check whether the AC pipe system is connected correctly and firmly, and there is no leakage. 

2. Check and confirm that the power distribution mode of UPS and PMU, connections of the power cables and the 
signal cables are correct, and that there is no short circuit. 

3. Check that the installation and cable connection of the batteries are correct, and that the positive pole and negative 
pole of the battery are correct. 

4. Measure and check that the voltage and frequency of the mains are normal. 

5. Check and confirm that all of the communication cables are connected correctly and firmly. 

6. Check and confirm that the remained unoccupied U height space is covered by the dummy plate. 

 

 

Warning 

1. Before startup of the SmartCabinet, ensure that the maintenance bypass air breaker on the MSC-PMU is off and locked by a 
metal latch. 
2. Before startup, ensure that the indicator of the SPD module is green. 

 

4.2   Startup 

The startup flow chart of SmartCabinet is shown in Figure 4-1.   

Closing

external input

power switch

Closing the air breakers of

total input on the PMU,

SPD, UPS output, PDU,

lighting & LCD in turn

Start up user

devices

Wait for LCD

startup, log in the

SmartCabinet

monitoring system

UPS startup

Closing input

air breaker

downstream

the UPS

 

Figure 4-1    Startup flow chart 

The startup procedures are as follows: 

1. Close the external input power switch. 

2. Close the input air breaker downstream the UPS. 

3. Close the main input air breaker on the MSC-PMU, SPD module air breaker, UPS input air breaker, AC input 
power air breaker, UPS output air breaker, lighting & LCD air breaker from left to right in turn, as shown in Figure 4-2. 

Summary of Contents for SmartCabinet

Page 1: ...ction unit is external For its using method refer to UF BFP 63A Backfeed Protection Unit User Manual Warning Backfeed Protection Before operating on the circuit first isolate the UPS and then check whether dangerous voltage exists between the ports as well as between the port and the ground Potential Risk 1 Only after all power is disconnected can you operate the inner components of the product 2 ...

Page 2: ...pter 3 Installation 13 3 1 Installing The Cabinet 13 3 2 Installing AC Components 13 3 2 1 Removing And Placing Outdoor Unit 14 3 2 2 Installing AC Outdoor Unit 15 3 2 3 Connecting Copper Pipes 17 3 2 4 Connecting Drain Pipe Of Indoor Unit 18 3 3 Installing UPS Power Supply System 19 3 3 1 Installing Battery Module 19 3 3 2 Installing UPS 20 3 4 Installing Fire Fighting Subrack Option 21 3 5 Insta...

Page 3: ... 1 License Page 38 5 2 Startup Page 38 5 3 SmartCabinet Homepage 39 5 4 Menu Items 40 5 4 1 Main Information of SmartCabinet 40 5 4 2 Environment 40 5 4 3 Power 43 5 4 4 Thermal 45 5 4 5 Setting 46 5 4 6 Log 49 Chapter 6 Web Page Of MSC C 52 6 1 Login Preparation 52 6 1 1 Checking IP Address Connectivity 52 6 1 2 Checking Browser Version 52 6 1 3 Checking Browser Setting 52 6 2 Log In MSC C 56 6 2...

Page 4: ...6 System Options 78 6 4 7 Help 86 Chapter 7 Maintenance 87 7 1 Safety Instructions 87 7 2 Maintenance Of The Main Components 87 7 2 1 MSC C Maintenance 87 7 2 2 AC System Maintenance 89 7 2 3 UPS Power Distribtuion System Maintenance 91 7 3 Disassembly 92 7 4 Troubleshooting 92 Appendix 1 Glossary 93 ...

Page 5: ...tacenter monitoring management platform of Emerson and is compatible with all series of Emerson products plug and play it also provides energy consumption analysis All these added valves can hardly be realized by separated purchase In all the product helps the customers build a green and healthy datacenter quickly This chapter expands the model description specification features appearance compone...

Page 6: ... a precision air conditioner AC for short cooperates with closed cold hot aisle technology to improve purposeful cooling in computer room The fan is embedded with mute design which can be used in office area zIntelligent monitoring intelligent control functions such as integrated environment monitoring device monitoring alarm linkage and so on provide centralized monitoring platform for computer r...

Page 7: ...nditioner host Emergency fan Monitoring and management card Sensors Alarm unit Figure 1 2 Schematic diagram of system composition Monitoring system Cooling and emergency system Power supply system Lighting system LCD display panel Air management kit Power distribution system Figure 1 3 Appearance and components 1 6 Functional Components The SmartCabinet mainly contains rack supporting system power...

Page 8: ...onment in the cabinet to be stable so that the IT devices can operate safely and reliably Emergency ventilation system Prevent high temperature partially inside the cabinet An emergency device that can start up automatically when over temperature occurs inside the cabinet or the air conditioner shuts down or fails to prevent the devices from operating in high temperature When the system is operati...

Page 9: ...hen the altitude is above 1500m with reference to GB T3859 2 For the air conditioner derating is required when the altitude is above 1000m Operation voltage range Single phase 198Vac 254Vac Note When the ambient temperature of the cabinet exceeds 35 C the cabinet loads should be derated to below 2800W 1 7 2 Storage Environment The storage environment requirements are listed in Table 1 5 Table 1 5 ...

Page 10: ...gh to go through the door together with the pallet To avoid damage to the equipment and the building measure the height of the cabinet and the door and confirm the clearance before moving it 2 1 Installation Tools Floating nut hook The floating nut hook is an accessory its appearance is shown in Figure 2 1 A A amplified Hook Figure 2 1 Floating nut hook The floating nut hook is used to install the...

Page 11: ... the level state when adjusting the cabinet Vacuum pump Used for pipe vacuum during AC installation process 2 2 Fittings The fittings are shown in Figure 2 5 See Table 2 2 for their usage Floating nut M5 countersunk head screw M6 panel screw M6 pan head screw Cable tie fixture kit Figure 2 5 Fittings Table 2 2 Usage of fittings Name Usage Floating nut Use together with M6 screw used to install the...

Page 12: ...t is recommended to choose railway or ship for transporting the cabinet AC indoor unit and AC outdoor unit If truck transportation is chosen choose preferable roads to avoid excess bumping The component with package is shown in Figure 2 6 See Table 2 4 for its ranges of dimensions and weight D H W Figure 2 6 Component with package Table 2 4 Ranges of dimensions and weight Component Range of dimens...

Page 13: ...e mechanical carrying tools to unload and carry them such as a hand pallet truck or an electrical forklift as shown in Figure 2 8 Hand pallet truck Electrical forklift Figure 2 8 Mechanical carrying tools When the hand pallet truck or the electrical forklift is used to unload and carry them it is recommended to forklift them on its center of gravity to avoid toppling over as shown in Figure 2 9 Fo...

Page 14: ...ing materials for further use or dispose of them properly Unpacking Move the equipment to the nearest place to the final installing site and then unpack it The unpacking procedures are as follows 1 Remove the packing materials 1 Move the equipment of assembled package to an open firm and level ground 2 Use a utility knife to cut off the packing strip on the package paper box carefully and remove t...

Page 15: ...slope and connect it with the pallet Pallet Slope Push the cabinet slowly from the pallet down to the ground along the slope Figure 2 12 Removing the pallet Note 1 When removing the pallet you need to prepare the slope or similar device by yourself 2 The whole cabinet is very heavy so take precautions when pushing the cabinet from the pallet down to the ground along the slope to avoid accidental c...

Page 16: ...r room should be free of corrosive gas and organic solvent Clearance When installation maintain sufficient clearance to facilitate installation and maintenance of the cabinet The distance from the front rear door to the wall or other obstacles must be larger than 1 0m The required clearance for opening the front and rear door is shown in Figure 2 13 90e 90e Front door Rear door 600 600 Figure 2 13...

Page 17: ...n the prearranged position and use a movable wrench to loosen the fixing nuts on the four feet bolts on the cabinet as shown in Figure 3 2 Clockwise Hexagon bolt Fixing nut Counter clockwise The feet rise Figure 3 2 Loosening the fixing nut 2 Rotate the hexagon head bolt on the bottom of the feet clockwise or counter clockwise till the feet rise or drop to an optimal position and use a gradienter ...

Page 18: ...the four screws on the four corners of outdoor unit and carry the AC outdoor unit out as shown in Figure 3 4 A A amplified Screw 4 pcs AC outdoor unit Supporting part of AC outdoor unit 2 pcs Figure 3 4 Removing the fixing screws of outdoor unit Note 1 In Figure 3 3 the two metal press strips on top of the outdoor unit can be used as horizontal cable organizers at back end of the cabinet 2 In Figu...

Page 19: ...Gas side pipe Heat insulation material Floor Drain pipe of condensate water extend to outdoor to drain condensate water 1 200 Cabinet Figure 3 5 Outdoor unit installed higher than indoor unit Outdoor unit Liquid side pipe no direct sunlight Wall bushing Isolation floor Sealing on inlets Gas side pipe Heat insulation material Floor Drain pipe of condensate water extend to outdoor to drain condensat...

Page 20: ... unit on top of the cabinet There is a special method for installing outdoor unit higher than indoor unit that is installing the outdoor unit on top of the cabinet The detailed installing procedures are as follows 1 Life or carry the outdoor unit removed from the cabinet onto top of the cabinet See Figure 3 8 for the installing direction of AC outdoor unit 2 Adjust the placing position of the AC t...

Page 21: ...ssor to avoid oil leakage and clogging in parts of the system and minimize noise and vibration to the greatest extend 4 Consult Emerson before installation on whether measures such as using extended piping kit are needed if the equivalent length exceeds 20m or if the vertical distance between the indoor unit and the outdoor unit exceeds the values in Table 3 1 Table 3 1 Vertical distance between i...

Page 22: ...g Use vibration isolating support to isolate the refrigeration pipes from the building 6 Use a soft and flexible material to pack around the pipes to protect them from damage caused by going through openings in walls and to reduce vibration transmission 7 Connect pipes of indoor and outdoor units according to the labels The unit uses quick connection mode 8 Adding refrigerant for long pipe system ...

Page 23: ...wer part of the cabinet it cooperates with the power management unit PMU for short it has been installed at top part of the cabinet installed in the same cabinet to realize mains input and power supply and distribution management function There are two versions for the UPS configured in the system domestic version and Asia Pacific LCD version For Asia Pacific version the UPS and the battery module...

Page 24: ...s accessories onto both sides of the front panel of the UPS as shown in Figure 3 12 Hanger 2 pcs Screw 6 pcs UPS Figure 3 12 Installing brackets 2 Place the UPS on the cabinet bracket pre installed push the UPS in to make the hangers align with the vertical poles Use four M6 16 screws to fix the UPS on the rack through the hangers as shown in Figure 3 13 M6 h16 screw 4 pcs UPS Bracket Figure 3 13 ...

Page 25: ...dle or lower part of the cabinet 3 4 Installing Fire Fighting Subrack Option 1 The fire fighting subrack is to be installed in the 3U space under the PMU power management unit Place the fire fighting subrack on the supporting rail of the cabinet 2 Push the fire fighting subrack in to make its hangers aligned with the vertical poles 3 Use four M6 16 screws to fix the fire fighting subrack on the ra...

Page 26: ...tem See Table 3 5 for the configuration of the SmartCabniet monitoring system Table 3 5 Configuration of the SmartCabniet monitoring system No Product name Quantity Product external model 1 MSC C card 1 MSC C C domestic version MSC C A Asia Pacific version 2 Intelligent tmperature sensor 2 IRM S01T 3 Water leakage detective belt sensor 1 IRM S01W 5m 4 Wireless Modem USB port optional 1 Baiyi 181M ...

Page 27: ...d the device number in serial connection cannot exceed 8pcs 3 6 2 Notes When installing MSC C take the following precautions to avoid personnel injury and device damage by accident zAlways cut off the power before performing any installation operation on the MSC C zEnsure that the external devices are connected to the correct MSC C ports zWear an ESD wrist wrap during installation zArrange the wir...

Page 28: ...used to insert the MSC C card into the intellislot intelligent card slot of the UPS Use screws to tighten it as shown in Figure 3 18 Intelligent card slot Baffle plate of intelligent card slot MSC C intelligent card Figure 3 18 Schematic diagram of installing MSC C card 3 6 3 Installing Sensors Note For the detailed installation guide of the sensors refer to IRM S01T Intelligent Temperature Sensor...

Page 29: ... installed on the cable holder on rear door of the cabinet as shown in Figure 3 20 Temperature sensor 4DIF sensor Figure 3 20 Installing temperature sensor and 4DIF sensor 3 Install water leakage sensor 1 Open the rear door of the empty cabinet stick the water leakage sensor onto the lower part of the cable organizer 2 Connect the water leakage detective belt lead and fasten the detective belt pro...

Page 30: ...rd 2 Stick the wireless Modem aerial that contains magnet onto the bottom plate of the hot aisle as shown in Figure 3 22 Aerial MSC C card Wireless Modem Figure 3 22 Installing wireless Modem 3 6 5 Adjusting Micro Switch There are micro switches on the upper right corner of the front and rear doorframes To prevent the micro switch from being pressed and damaged by the door during transportation be...

Page 31: ...ommunication cable separately on the cable organizers on both sides in the rear space of cabinet It is recommended to manage the power cable on the right cable organizer and manage the communication cables on the left cable organizer The wiring of PMU UPS PDU intelligent emergency fan unit and AC power inside the cabinet has been completed before delivery You only need to connect the cable between...

Page 32: ... 4 Connect L line N line and PE line of the output cable W02 Output respectively to the output live line terminal L output neutral line terminal N and output ground line terminal PE of the UPS I O terminal block and tighten the fixing screws as shown in Figure 3 25 5 Ensure that the input live line terminal V input live line terminal W and input live line terminal U1 have been shorted by using the...

Page 33: ...telligent card slot on rear panel of the UPS to the corresponding ports of MSC C card as shown in Figure 3 27 Connect the cable W08B to the COM1 port of MSC C card and connect the cable W12 COM2 to the COM2 port of MSC C card UPS䗃ࠪ UPS OUPUT UPS䗃 ޕ UPS INPUT COM1 COM2 LAN USB UPS MSC C PE W12 COM2 W08B COM1 Communication wiring Figure 3 27 Cable connection of COM port of MAC C card 3 7 4 Connectin...

Page 34: ...ble into the cable entry hole of total input cable and restore the cover plate 3 7 5 Connecting Cables Of Indoor And Outdoor Units 1 Open the cover plate for cable connection of the outdoor unit lead the connecting cable 5 core 7m between the indoor unit and the outdoor unit and the 485 control cable 2 core insert type 7m through the cable entry hole on the cover plate and connect the cable to the...

Page 35: ... the cabinet a wrench is recommended 3 If there is no earth block in the building where the SmartCabinet is placed you can use a yellow green earth cable of no less than 6mm2 to connect the earth terminal of cabinet with that of PMU total input to ensure reliable earthing of the cabinet 3 8 Configure Communication Address And Port 1 Set the addresses of the temperature sensor through the DIP switc...

Page 36: ...uch as velcro strip standard cable management unit Note 1 The U height space which is not occupied by equipment should be covered by the dummy panel 2 After the cable layout is completed use sealant to seal the used cable entry holes to keep the cabinet be airtight The optional accessories of the cabinet are given in Table 3 10 Table 3 10 Optional accessories Name Description Appearance Velcro str...

Page 37: ...rt rails can be adjusted to satisfy different installation depth Installation hole 8 pcs Heavy duty pull out shelf Applicable to server cabinets capable of bearing more than 80kg 1U height the telescopic rails can be adjusted to satisfy different installation depth equipped with a handle and positioning pins Installation hole 8 pcs Fastener 4 pcs 2U drawer Applicable to server cabinets capable of ...

Page 38: ...dummy plate Tool less installation mode Installation hole 4 pcs 5U dummy plate Tool less installation mode Installation hole 4 pcs 6U dummy plate Tool less installation mode Installation hole 4 pcs 1U dummy plate with brush Non tool installation mode selected for front cabling of the cabinet Installation hole 2 pcs ...

Page 39: ... cables are connected correctly and firmly 6 Check and confirm that the remained unoccupied U height space is covered by the dummy plate Warning 1 Before startup of the SmartCabinet ensure that the maintenance bypass air breaker on the MSC PMU is off and locked by a metal latch 2 Before startup ensure that the indicator of the SPD module is green 4 2 Startup The startup flow chart of SmartCabinet ...

Page 40: ...nd wait about 30s the UPS will switch to inverter standby mode and the INVERTER indicator will blink When the UPS has output the INVERTER indicator will turn on as shown in Figure 4 3 b a b Figure 4 3 Indicator state 6 Measure whether the inverter output voltage is normal 7 After the UPS inverter output becomes normal the LCD on the front door will get power and start up Log in the SmartCabinet mo...

Page 41: ...The power off procedures are as follows 1 Ensure that all user IT equipment are powered off 2 Enter the Hot Management menu of the LCD monitoring system to turn off the AC 3 After the AC stops flowing cold wind open the AC air breaker on the PMU 4 Press the OFF key on the display panel of the UPS 5 Open the UPS input and output air breakers 6 Open the total input air breaker on the PMU 7 Check tha...

Page 42: ...gure 5 1 Figure 5 1 License page 2 The authorized commissioning engineer calls the customer service hotline of Emerson Network Power Co Ltd 400 887 6510 to get the password 3 Type the gotten password in the textbox of License and then click OK 4 If the authorization is a success the system will jump to the login page automatically Note For Asia Pacific version there is no need of authorizing so th...

Page 43: ...ge will jump to the system homepage automatically without any operation 5 3 SmartCabinet Homepage The SmartCabinet homepage is shown in Figure 5 3 Figure 5 3 SmartCabinet homepage On the SmartCabinet homepage the menu items include System Environment Power Thermal Setting and Log The system menu structure of the display panel is shown in Figure 5 4 ...

Page 44: ...per part the system page will appear displaying air flow status cabinet cold aisle temperature hot aisle temperature AC status and UPS status as shown in Figure 5 5 Figure 5 5 System page The system page is divided into four parts the left part displays air flow cycle mode of SmartCabinet front door temperature and rear door temperature the upper right part displays thermal management mode inside ...

Page 45: ...ys front door on off status rear door on off status and water leakage status Clicking the Setting submenu can view the setting signal of environment temperature If the current user does not have the authority the login dialog box will pop up as shown in Figure 5 7 Figure 5 7 Login dialog box Use admin to log in the system the page will jump to the setting page automatically as shown in Figure 5 8 ...

Page 46: ...e edit box a digit keyboard will pop up type the valve you want to set and click the Enter button on the digit keyboard as shown in Figure 5 9 the typed valve will be sent to the device Note The default valves of temperature alarm are as follows The alarm upper limit of front door temperature sensor is 35 C and the alarm lower limit is 0 C the alarm upper limit of rear door temperature sensor is 4...

Page 47: ...s as shown in Figure 5 11 The setting operation is the same as that of environment temperature Figure 5 11 Power setting page Click the Control submenu in the left part the control page appears as shown in Figure 5 12 You can realize on off control over each place of the PDU through clicking the OFF ON icon When the icon is green and displaying ON status it indicates that the PDU output status is ...

Page 48: ...y power for the emergency fan The available PDU socket number is 22 places for the user Figure 5 12 Power control page Click the Control submenu the confirmation dialog box shown in Figure 5 13 pops up to require your second time confirmation about the control operation Click OK to execute the control operation as shown in Figure 5 14 Figure 5 13 Second time confirmation about the power control ...

Page 49: ...5 15 Figure 5 15 Thermal status page Click the Thermal submenu at the left part the thermal page will appear as shown in Figure 5 16 You can click the OFF ON icon in the Power On Off field to realize AC on off control in the SmartCabinet The control and operation mode of AC on off is the same as that of power control the setting operation of Temperature Setting and Temperature Accuracy is the same...

Page 50: ...Setting Language and Information Password Click the Password submenu under the Setting menu the page shown in Figure 5 17 pops up Figure 5 17 Password page Click the input box the user login dialog box will pop up After login by using admin only the user that has the control authority can perform password modification type the Password New Password1 and New Password2 and click the Set button to co...

Page 51: ... WEB page through IE browser on the System Options Restore System page click the Restore LCD Password button the LCD will display the page shown in Figure 5 19 click the Restore Default button the password of the LCD display panel will be restored to default 1234 Figure 5 19 Password page IP Setting Click the IP Setting submenu under the System menu the page shown in Figure 5 20 will pop up ...

Page 52: ...ontrol system for setting new IP Figure 5 21 IP setting On the page shown in Figure 5 21 you can configure the network parameters of the MSC C background monitoring unit such as IP Address Subnet Mask and Default Gateway click the Set button to make the parameters effect Note After modifying the IP address if you want to visit the MSC C through network mode please use the new IP address for login ...

Page 53: ...e 5 23 pops up Through the page you can view the current system information including System Name Hardware Version Software Version Serial Number and Service Hotline Figure 5 23 Information page 5 4 6 Log Alarm management 1 Display an alarm On any page if the current system has an alarm in the lower part of the page an alarm rolling bar will appear to display the current alarm as shown in Figure 5...

Page 54: ...arm sound If you want to turn off the alarm sound click the button Click the alarm rolling bar the page will jump to the real time alarm page as shown in Figure 5 25 Figure 5 25 Real time alarm page 2 History alarm Click the His Alarm submenu under the Log menu to view the historical alarms as shown in Figure 5 26 You can query the historical alarms within a week ...

Page 55: ...tion User Manual Figure 5 26 Historical alarm page Ctrl Info Click the Ctrl Info submenu under the Log menu to view the historical control records as shown in Figure 5 27 You can query the historical control information within a week Figure 5 27 Control information page ...

Page 56: ...ivity Refer to Q1 in FAQ in 7 2 1 MSC C Maintenance for the test method 6 1 2 Checking Browser Version The recommended browser version includes IE7 IE8 IE9 or IE10 6 1 3 Checking Browser Setting Checking IE General setting Double click the icon of IE to run the software click the menus of Tools Internet Options then click the Settings button on the General tab and select Every time I visit the web...

Page 57: ...in Figure 6 3 Figure 6 3 LAN setting 3 Consult the network manager of your area ask if you need to set a proxy server and get the configuration method If there is no need to set a proxy server do not tick any option Checking IE security setting 1 Double click the icon of IE to run the software click the menus of Tools Internet Options and then choose the Security tab to pop up the window shown in ...

Page 58: ...6 4 choose Trusted sites and click the Custom level button to pop up the window shown in Figure 6 5 Figure 6 5 Security setting 2 3 In the window shown in Figure 6 5 set Medium low for the security level Click the Reset button to finish Reset custom settings at last click OK 4 In the window shown in Figure 6 6 set Enable for File download ...

Page 59: ...e 6 6 Enabling file download 5 In the window shown in Figure 6 7 set Enable for Initialize and script ActiveX controls not marked as safe for scripting Figure 6 7 Enabling ActiveX controls 6 In the window shown in Figure 6 8 add the IP address of the MSC C into the trusted site list ...

Page 60: ...f the authorizing boot strap page does not appear refer to Q5 in FAQ in 7 2 1 MSC C Maintenance Figure 6 9 Authorizing boot strap page 2 Call the customer service hotline of Emerson Network Power Co Ltd 400 887 6510 tell the code to the customer service personnel and you will get the password 3 Type the gotten password in the textbox of Password and then click OK If the password is correct the sys...

Page 61: ...ing and set the IE browser again 6 2 3 Getting Password If you forget the password click the Forget Password button on the login page and the screen will display the page of getting password as shown in Figure 6 11 Figure 6 11 Page of getting password Type your username and click the Get Password button your password will be sent to the email box or phone which you have configured before Clicking ...

Page 62: ...cation Note When the system is operating abnormally a corresponding fault or alarm will occur The emergency ventilation system can prevent continuous temperature rise inside the cabinet within a short time If the high temperature fault or alarm has not been eliminated for a long time you need to go to the field and open the front and rear doors of the cabinet meanwhile contact the customer service...

Page 63: ...yed in the lower box You can select the device signals to be displayed according to your needs however the selected signals cannot exceed 4 At last click OK Figure 6 14 Display setting Note There is no need of setting the display mode of temperature humidity and 4DI signals and the effective signals will be directly displayed on the page 2 Save Click the Save button all configuration will be saved...

Page 64: ...status Click Clear Time out the input box shown in Figure 6 16 will appear After typing the password the controllable status will become normal after about 5s Figure 6 16 Dialog box of Security authentication 6 3 4 Logout Click the Logout link at the upper right corner of the homepage the prompt box shown in Figure 6 17 will appear clicking OK will log out safely Figure 6 17 Logout 6 3 5 Real Time...

Page 65: ...6 18 1 4 2 5 6 7 3 8 9 10 1 Signal configuration icon 2 Remove component icon 3 Back to browse icon 4 Component list 5 Save icon 6 Effective to same type of equipment icon 7 Restore icon 8 View history chart icon 9 History data selection icon 10 View real chart icon Figure 6 18 Overview tab In editing status clicking the icon can restore default clicking the icon can configure the same type of oth...

Page 66: ... 6 20 Control signals Select an option from the drop down box of Value Setting and click the Set button to control the device Setting Clicking the Setting tab can enter the setting page which displays setting signals of selected device as shown in Figure 6 21 Figure 6 21 Setting signals You can set several signals at the same time and at most 16 signals can be set at the same time for each time No...

Page 67: ...s 6 4 2 Safe Shutdown On the MSC C homepage click the Safe Shutdown menu on the left two submenus appear including Shutdown Schedule and Server Shutdown Shutdown Schedule Click Shutdown Schedule submenu under the Safe Shutdown menu the page shown in Figure 6 23 pops up Figure 6 23 Shutdown Schedule page The Shutdown Schedule page is used to add delete and modify schedule shutdown task of UPS devic...

Page 68: ...ort up to ten shutdown tasks 2 Only when Enable Device is set for Field can the schedule shutdown task be enabled Server Shutdown Click Server Shutdown submenu under the Safe Shutdown menu the Server Shutdown page will pop up as shown in Figure 6 25 Figure 6 25 Server Shutdown page On the Server Shutdown page you can add and delete server shutdown task The procedures for adding a server shutdown t...

Page 69: ... 2 Click the Acknowledge button to confirm the alarm The confirmed alarm will not participate in alarm linkage and the alarm notification is sent once only 3 When the mouse is located on the Confirmed link the alarm confirming information will be hovered when you move the mouse the information will disappear as shown in Figure 6 27 Figure 6 27 Confirming information History Alarm Click History Ala...

Page 70: ... and customize the alarm content including Equip name Alarm description Alarm TIME and Alarm state by default Click the Save button to finish the alarm configuration When an alarm is generated the system will notify users through the chosen notification method Note 1 Users must tick the notification method first in the Notification by check boxes and then the alarm table below can be edited 2 When...

Page 71: ...can perform SMS Modem Configuration and RDU Voice Notification System Setting for alarm notification reminding through SMS or phone you can also perform Email Server Configuration for alarm notification reminding through email the procedures are as follows zSMS Modem Configuration 1 Connect an SMS Modem through USB port according to need and choose Port Type the page will display Parameter automat...

Page 72: ...t 3 When using SSL you need to ensure that the Email server supports SSL function 3 Scheduled Notification Configuration Click the Alarm Notification submenu under the Alarm Management menu and then click the Scheduled Notification Configuration tab the page shown in Figure 6 31 pops up Figure 6 31 Scheduled notification configuration Note 1 Scheduled notification configuration must be used togeth...

Page 73: ...rm linkage configuration 2 Firstly select a command for instance OR In this case the expression is signal 1 Input1 Register OR signal 2 Input2 Register signal 3 Output Register Secondly when Signal is chosen for the input and output parameters first choose the equip name from the drop down lists of Equip Register then choose the signal type from the drop down lists of Signal Type at last choose th...

Page 74: ...iguration 4 The operator usages in the alarm linkage are listed in Table 6 1 Table 6 1 Operator usages in the alarm linkage Operator Input 1 Input 2 Param1 Param2 Output Expression SET P1 Sout Rout SET_ _P1_Output AND Sin1 Rin1 Sin2 Rin2 Sout Rout Sin1 Rin1 AND Sin2 Rin2 Sout Rout OR Sin1 Rin1 Sin2 Rin2 Sout Rout Sin1 Rin1 OR Sin2 Rin2 Sout Rout NOT Sin1 Rin1 Sout Rout Sin1 Rin1 NOT Sout Rout XOR ...

Page 75: ...d logs for the user On the MSC C homepage click Data History in the left part three submenus appear including Device Information History Data and History Log Device Information Click the Device Information submenu under the Data History menu the page shown in Figure 5 41 pops up The page includes two tabs Device Information List and Export SNMP MIB 1 Device Information List As shown in Figure 6 36...

Page 76: ...e History Data and set the start time and the end time for instance from 2014 07 30 00 00 00 to 2014 07 30 23 59 59 Then click the Query button all the history data during the time will be listed click the Download button to download the query result 2 Historical Curve As shown in Figure 6 39 choose a device for instance TDI and the Log Type for instance Front Temp and set the start time and the e...

Page 77: ...instance from 2014 07 30 00 00 00 to 2014 07 30 23 59 59 Then click the Query button all control logs during the time will be listed click the Download button to download the query result Note When the log type is selected as System Log or Driver Log after clicking the Query button the query result will not be displayed on the page instead it will be directly downloaded as a zip file 6 4 5 Device ...

Page 78: ...dresses under the same port number must be different for some device types you need not type the device address at this point the Device Address textbox turn gray and cannot be edited When one kind of device has many models you need to type the model ID which must be numbers from 1 to xx The model IDs under one kind of device must be different 5 Choose or type the device location 6 Type the commun...

Page 79: ...lick the Save Configuration button to make the settings become effective and the detailed procedures are the same as those of adding a new device Note Before clicking the Delete button if the device information has been modified it cannot be deleted zModifying a device 1 Choose the device which needs to be modified in the device list 2 Modify the device information 3 Click the Modify button to mak...

Page 80: ...Click the Uninstall button the confirming dialog box pops up as shown in Figure 6 46 Figure 6 46 Confirming dialog box Click OK the dialog box of Security authentication pops up as shown in Figure 6 16 type the login password of current user and click OK to uninstall the corresponding equipment type Note 1 While installing device type if the device type exists and the device driver has a higher ve...

Page 81: ...e list at upper part of the page After all modifying is done click the Save Configuration button to save the asset information Note For the newly added device its default asset information is Signal Setting Click the Signal Setting submenu under the Device Options menu the page shown in Figure 6 48 pops up Figure 6 48 Modify device name On the page shown in Figure 6 48 you can modify the device na...

Page 82: ...y of batch configuration If you fail in performing batch configuration please click Show Help to view the help information 2 The batch configuration file is encrypted after downloaded to local 6 4 6 System Options On the MSC C homepage click the System Options menu in the left part eight submenus appear including Monitoring Unit Network Setting User Management Date Time Setting Restore System Site...

Page 83: ...cked will be automatically cleared in 24h Network Setting 1 IP Setting Click the Network Setting submenu under the System Options menu the page shown in Figure 6 52 pops up Figure 6 52 IP setting On the page shown in Figure 6 52 you can configure the network parameters such as IP addressing mode IP Mask Default Gateway DNS1 Preferred DNS server and DNS2 Alternate DNS server After modifying the net...

Page 84: ...etting submenu under the System Options menu and then click the SNMP Configuration tab you can configure SNMP agent The MSC C system supports V2 and V3 versions of SNMP agent As shown in Figure 6 54 the specific setting method of SNMP V2 is as follows 1 Set NMS IP host IP address of SNMP agent data receiving end 2 Set Trap Level Enable or disable 3 Keep defaults for other items Figure 6 54 SNMP V2...

Page 85: ... Authentication Password and Privacy Password which contain at least 8 characters and be the same as the password set by the host of SNMP agent data receiving end or it cannot be decrypted and received After parameter setting click the Add button to add NMS If you need to modify NMS setting select the NMS which needs to be modified modify the setting and then click the Modify button to save the se...

Page 86: ...ive only under the precondition that the remote service has been established otherwise a prompt of failure will pop up after you click OK zReplace Host used to replace the local host during remote service When the host that has established remote service need to quit but you want to remain the established remote service relationship you need to replace the local host to participate in the remote s...

Page 87: ...Level C Engineer The engineers can get the following access Send control command to intelligent equipment Browsing controlling and modifying parameters Download files Modifying user information of their own Level D Administrator The administrator can get full access Send control command to intelligent equipment Browsing controlling and modifying parameters Upload and download files Modifying addin...

Page 88: ...button to make the setting effective Figure 6 59 Date time setting The MSC C can also get the local time Choose Specify Date Time click the Local Host Time button to get the local time and then click the Set button to make the new time effective Note Time calibration adopts Specify Date Time by default Restore System Click the Restore System submenu under the System Options menu the page shown in ...

Page 89: ... the page shown in Figure 6 61 pops up Figure 6 61 Site information setting On the page shown in Figure 6 61 you can modify the site information of MSC C including Site Name Site Location and Site Description System Upgrade Click the System Upgrade submenu under the System Options menu the page shown in Figure 6 62 pops up Figure 6 62 System upgrade On the page shown in Figure 6 62 click the Brows...

Page 90: ...y uploading system Logo picture Click the Browse button choose the needed Logo picture and click the Upload button to upload the file to MSC C Only gif bmp jpg and png format pictures are allowed and the picture size should be less than 500K Clicking the Default button can restore the default Logo picture 6 4 7 Help On the MSC C homepage click the Help menu in the left part one submenu appears Abo...

Page 91: ...idation of warranty 3 Ignoring the safety instructions will endanger personnel safety and environment 4 Unsuitable components will lead to performance decrease or equipment shutdown it is commended to use the components made by Emerson 7 2 Maintenance Of The Main Components Note Regular maintenance inspection are necessary to ensure proper operation of the equipment 7 2 1 MSC C Maintenance Restori...

Page 92: ...nd the method is as follows 1 Click the icon at the lower left corner and type cmd in the textbox as shown in Figure 7 2 Figure 7 2 Typing cmd 2 Press the Enter key the page shown in Figure 7 3 pops up Type ping and IP address in the command line for instance ping 10 163 162 135 and check whether the communication is successful Figure 7 3 Communication test Step 3 If the above mentioned steps cann...

Page 93: ...oring A The SmartCabinet supports connection to RDU M centralized monitoring platform of Emerson See Figure 7 4 for the networking mode of several SmartCabinet Figure 7 4 SmartCabinet networking topology diagram 7 2 2 AC System Maintenance The AC system maintenance includes electric inspection indoor unit maintenance outdoor unit maintenance and maintenance inspection checklist Note Switch off the...

Page 94: ...now to accumulate around the side or underneath the condenser Check for bent or damaged fins and simply repair them if necessary Check all refrigerant pipes and capillaries for vibration and support them if necessary Carefully inspect all refrigerant pipes for signs of oil leakage thus determining the leakage position 3 Compressor The compressor fault is generally classified into two types zMotor ...

Page 95: ...or 20000 hours 40000 hours continuously The higher the environmental temperature is the shorter the fan life will be During UPS operation verify the fan status once every half a year by confirming that the airflow can blow out from the ventilation holes on the rear panel of the UPS Checking UPS status Clean the UPS periodically especially the ventilation holes to ensure free airflow inside the UPS...

Page 96: ...ot installed well or damaged Readjust the installation clearance or call the customer service hotline of Emerson 4008876510 Water leakage detective belt sensor alarm There are water in the detection belt area Check the leaking place in the computer room AC condensate water leakage Check that the connection of the condensate water pipes is reliable PDU over load alarm PDU exceeds the load setpoint ...

Page 97: ...ditioner PDU Power distribution unit PMU Power Management Unit UPS Uninterruptable power supply DI Digital Input IE Internet Explorer a Web browser developed by Microsoft FAQ Frequently Asked Questions LCD Liquid Crystal Display LED Light Emitting Diode RCCB Residual Current operated Circuit Creaker ...