22 Chapter 3 Installation
SmartCabinet Integrated Solution User Manual
Fixing button
(2 pcs)
PDU
Cable
organizer
Cable
organizer
PDU
Installing PDU
Installation hole
Figure 3-15 PDU tool-less installation
Note
1. When using top cabling method, make the cable outlet end of the PDU upward and vertical.
2. When removing the PDU from the cabinet, use force evenly to make the PDU slide upwards vertically until the fixing buttons
are divorced from the installation hole.
3. Refer to
Liebert MPS PDU User Manual
for other installation modes.
Warning
When using the PDU, pay attention to the power distribution capacity of single PDU and the threshold current of each power
distribution output port. The overload use is prohibited.
3.6 Installing SmartCabniet Monitoring System
See Table 3-5 for the configuration of the SmartCabniet monitoring system.
Table 3-5 Configuration of the SmartCabniet monitoring system
No.
Product name
Quantity
Product external model
1
MSC-C card
1
MSC-C-C (domestic version)/MSC-C-A
(Asia-Pacific version)
2
Intelligent tmperature sensor
2
IRM-S01T
3
Water leakage detective belt sensor
1
IRM-S01W (5m)
4
Wireless Modem (USB port, optional)
1
Baiyi-181M
5
Intelligent digital input sensor with RJ45 ports
2
IRM-S04DIF
3.6.1 Installing MSC-C Card
The MSC-C card is a Web/SNMP intelligent device monitoring card, which can monitor the system state of intelligent
devices, record alarm events, and notify the user of the intelligent device alarms through email or SMS mode. The
MSC-C card also enables you to set operating parameters and view device states through the embedded Web HMI,
moreover, it can send the states of the monitored intelligent devices to the network management software (NMS)
through SNMP protocol mode.