11.5.6 TorqueActual
Returns the actual load on the motor as a percentage of the rated motor load. This
attribute has 1 decimal place fixed precision, so a value of 1000 represents 100.0 %
load.
Get
Pr
04.020
11.5.7 TorqueRef
Sets the load (torque) reference as % of rated motor load (torque). This attribute has 1
decimal place fixed precision, so a value of 1000 represents 100.0 % load.
Set
Pr
04.008
= TorqueRef / 10
Get
Torque Ref = Pr
04.008
* 10
11.5.8 RefFromNet
Indicates the source of the speed reference.
TRUE if Pr
01.049
= 3 and Pr
01.050
= 1
FALSE otherwise.
Name:
TorqueActual
Class
0x2A
Default
Instance
0x01
Data Type
USINT
Attribute
0x0B
Access
Get
Name:
TorqueRef
Class
0x2A
Default
Instance
0x01
Data Type
USINT
Attribute
0x0C
Access
Get/Set
Name:
RefFromNet
Class
0x2A
Default
Instance
0x01
Data Type
USINT
Attribute
0x0C
Access
Get