Diagnostics
12.1
Overview
This section provides basic diagnostic information intended to resolve the most
common problems encountered when setting up an SI-DeviceNet module on a
DeviceNet network.
A high percentage of problems reported are basic set-up problems which can usually be
solved by reading the information in this chapter. If after reading this chapter you are still
experiencing problems, please contact your supplier for support.
12.1.1 Drive trip display codes
If the option module detects an error during operation, it will force a trip on the drive.
However, the trip string displayed on the drive will only indicate which slot initiated the
trip. The exact reason for the trip will be indicated in the drive trip code parameters
(Pr
10.020
and Pr
10.070
).
Table 12.1 shows the possible trips that will be displayed on the drive when a problem is
detected with the option module or when the option module initiates a trip.
Table 12.1 Drive trip display codes
Trip
Description
SlotX HF
The drive has detected that an option module is present but is unable
to communicate with it due to a hardware fault.
SlotX Error
User trip generated by the option module
SlotX Not
Fitted
This trip will occur if a drive slot was previously configured with an
option module but on power up, no option module was detected.
SlotX Different
This trip will occur if a drive slot was previously configured with an
option module but on power up, a different option module was
detected. Replacing the option module with another one of the same
ID number will not initiate this trip.
The trip will also occur if an option module is installed to a previously
unused slot.