SI-DeviceNet User Guide
Issue Number: 2
5.2
Parameter save and restore
Parameters in the module are saved when a normal drive parameter save is initiated by
selecting "Save Parameters" or setting a value of 1000 in Pr
mm.000
and performing a
drive reset. (If the drive is in the under voltage state or is supplied from a low voltage
power supply then a value of 1001 must be set in Pr
mm.000
and a drive reset
performed).
Any user-saved parameters in the option module's internal menus are stored in non-
volatile memory on the module and not in the drive. Therefore, if the module is moved to
a different slot or to a different drive, then any saved parameter values will follow the
module. If a module is to be replaced, ensure that the parameter values for the module
have been backed up before replacing it.
5.3
Module reset
A reset of the SI-DeviceNet module can be performed by the methods detailed below.
•
Set Pr
S.00.007
(or
Pr MM.007
) to On (1). This will only reset the module in slot S.
•
Select "Reset modules" or set a value of 1070 in Pr
mm.000
, and performing a drive
reset. This will perform a reset of all option modules installed in the drive.
5.4
Restoring module parameter default values
Setting Pr
S.00.008
(or Pr
MM.008
) to On (1) and performing a module reset will return
all parameters in the SI-DeviceNet module to their default values.
Parameters in the SI-DeviceNet module will also be set to their default values when
drive parameters are returned to their default values.
5.5
Single Line Parameters
Table 5.1 Menu 0 Setup
Parameter
Range(
Ú
)
Default(
Ö
)
Type
MM.001
Module ID
0 to 999
447
RO Num ND
NC
PT
MM.002
Software Version
00.00.00.00
to
99.99.99.99
RO Num ND
NC
PT
MM.003
Hardware Version
00.00 to 99.99
RO Num ND
NC
PT
MM.004
Serial Number LS
0 to 99999999
RO Num ND
NC
PT
MM.005
Serial Number MS
0 to 99999999
RO Num ND
NC
PT
MM.006
Module status
Initialising (0), OK (1),
Config (2), Error (3)
RO Num ND
NC
PT
MM.007
Module reset
Off (0) or On (1)
Off (0)
RW
Bit
NC
MM.008
Module default
Off (0) or On (1)
Off (0)
RW
Bit
NC