12.1.2 Module error codes
If the option module detects an internal error during operation, it will force a trip on the
drive and provide a sub-trip string for a clearer definition of the trip. The table below
shows the possible module error codes.
Table 12.2 Module error codes
12.1.3 DeviceNet error codes
If the SI-DeviceNet module detects a DeviceNet error during operation, it will force a trip
on the drive and provide a sub-trip string for a clearer definition of the trip. The table
below shows all possible SI-DeviceNet error codes.
Table 12.3 DeviceNet network error codes
Value
Text
Description
200
SW fault
Software fault
201
BG Orun
Background task overrun
202
FW invalid
Invalid firmware for hardware version
203
Drv unknown
Unknown drive type
204
Drv unsupported
Unsupported drive type
205
Mode unknown
Unknown mode
206
Mode unsupported Unsupported mode
207
FLASH corrupt
Corrupted Non-volatile Flash
208
Dbase init
Database initialization error
209
FS init
File system initialization error
210
Memory alloc
Memory allocation error
211
Filesystem
File system error
212
Configuration
Configuration file error
213
OHt
Overheated
214
TO drv
The drive has not responded with the watchdog period
215
eCMP
eCMP comms failure
216
TO eCMP slot 1
Slot 1 eCMP timeout
217
TO eCMP slot 2
Slot 2 eCMP timeout
218
TO eCMP slot 3
Slot 3 eCMP timeout
219
TO eCMP slot 4
Slot 4 eCMP timeout
220
Fact Setting
Missing factory setting
221
Config Load
Error loading saved configuration file
222
RT Config
Failed to update parameter after drive mode being
changed
223
Read Par
Failed to read parameter during cyclic communication
224
Write Par
Failed to write parameter during cyclic communication
Value
Text
Description
0
No trip
No trip
100
Link Loss
The link to the network has been lost
101
Bus Off
The CAN layer of the module has entered the Bus Off state