SI-DeviceNet User Guide
Issue Number: 2
11.4.8 FaultRst
Resets the drive from a tripped condition.
Set True Pr
10.038
= 100
Set False No action
11.4.9 FaultCode
If the drive is tripped, the fault code is obtained from parameter Pr
10.020
in the drive. If
the fault code in Pr
10.020
is one of the following, the table gives the appropriate ODVA
code, otherwise the error code will be returned as Pr
10.020
.
Fault codes
11.4.10CtrlFromNet
Indicates that the drive is operating under fieldbus control.
Get
Pr
06.042
bit 7 & Pr
06.043
Name:
FaultRst
Class
0x29
Default
Instance
0x01
Data Type
USINT
Attribute
0x0C
Access
Set
Name:
FaultRst
Class
0x29
Default
N/A
Instance
0x01
Data Type
USINT
Attribute
0x0D
Access
Set
Drive fault code
ODVA fault code
2
0x3210
3
0x2300
4
0x7112
6
0x9000
20
0x2310
21
0x4300
26
0x5112
32
0x3130
Name:
CtrlFromNet
Class
0x29
Default
Instance
0x01
Data Type
USINT
Attribute
0x0F
Access
Get