79
Reference Manual
00809-0200-4728, Rev RA
Section 6: Troubleshooting
April 2015
Low or No
Output
Sensor
Element
Connect a Field Communicator and enter the transmitter test mode to isolate
a sensor failure.
Check the process variable to see if it is out of range.
Loop
Wiring
Check for adequate voltage to the transmitter. It should be 12.0 to 42.4 Vdc
(over entire 3.75 to 23 mA operating range).
Check for shorts and multiple grounds.
Check for proper polarity at the signal terminal.
Check the loop impedance.
Connect a Field Communicator and enter the Loop test mode.
Check wire insulation to detect possible shorts to ground.
Electronics
Connect a Field Communicator and check the sensor limits to ensure
calibration adjustments are within the sensor range.
Table 6-1. Rosemount 644 Troubleshooting Table for 4-20 mA Output
Symptom or
issue
Potential
source
Corrective action