73
Reference Manual
00809-0200-4728, Rev RA
Section 5: Operation and Maintenance
April 2015
From the
HOME
screen, enter the Fast Key sequence.
Performing an analog output trim using AMS Device Manager
1.
Right click on the device and select
Service Tools
.
2.
In the left navigation pane select
Maintenance
.
3.
Find the
Analog Calibration
tab and click on the
Analog Trim
button.
4.
Follow the screen prompts through the Analog Trimming process.
Performing an analog output trim using LOI
Reference the below image for guidance on where to find Analog Trim in the LOI menu.
Figure 5-5. Trimming the Analog Output with the LOI
5.5.3
Performing a scaled output trim
The
Scaled Output Trim
matches the 4 and 20mA points to a user-selectable reference scale
other than 4 and 20 mA (2–10 volts, for example). To perform a scaled D/A trim, connect an
accurate reference meter to the transmitter and trim the output signal to scale as outlined in the
procedure.
Performing an analog output trim using a Field Communicator
1.
Connect an accurate reference meter to the transmitter at the
CONNECT REFERENCE
METER
prompt by shunting the power to the transmitter through the reference meter
at some point in the loop.
From the
HOME
screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
3, 4, 5, 1
Device Dashboard Fast Keys
3, 4, 5, 2
CALIBRAT
CALIBRAT
DAMPING
VARIABLE MAP
TAG
ALM SAT VALUES
PASSWORD
....
VIEW CONFIG
SENSOR CONFIG
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
SENSOR 1 CALIB
SENSOR 2 CALIB*
ANALOG TRIM
ANALOG TRIM
FACTORY RECALL
BACK TO MENU
EXIT MENU
....