Reference Manual
00809-0200-4728, Rev RA
Section 2: Configuration
April 2015
2.2.1
Warnings
2.3
System readiness
Confirm HART revision capability
If using HART based control or asset management systems, confirm the HART
capability of those systems prior to transmitter installation. Not all systems are capable
of communicating with HART Revision 7 protocol. This transmitter can be configured
for either HART Revision 5 or 7.
For instructions on how to change the HART revision of your transmitter, see
.
2.3.1
Confirm correct device driver
Verify the latest Device Driver files are loaded on your systems to ensure proper
communications.
Download the latest Device Driver at www.emersonprocess.com or
www.hartcomm.org
Failure to follow these installation guidelines could result in death or serious injury.
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
Before connecting a Field Communicator in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
Verify the operating atmosphere of the transmitter is consistent with the appropriate
hazardous locations certifications.
All connection head covers must be fully engaged to meet explosion-proof
requirements.
Process leaks could result in death or serious injury.
Do not remove the thermowell while in operation.
Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
Table 2-1. Rosemount 644 Device Revisions and Files
Software date
Identify device
Find device driver files
Review
instructions
Review
functionality
Date
NAMUR Software
Revision
HART Software
Revision
HART Universal
Revision
(1)
(1) NAMUR Software Revision is located on the hardware tag of the device. HART Software Revision can be read using a HART communication tool.
Device
Revision
(2)
(2) Device Driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to continue to
communicate with new HART devices. To access new functionality, the new Device Driver must be downloaded. It is recommended to download the new
Device Driver files to ensure full functionality.
Manual Document
Number
Changes to
Software
(3)
(3) HART Revision 5 and 7 Selectable. Dual Sensor support, Safety Certified, Advanced Diagnostics (if ordered), Enhanced Accuracy and Stability (if ordered).
June 2012
1.1.1
01
5
8
00809-0100-4728
See footnote 3 for
list of changes
7
9
Summary of Contents for Rosemount 644
Page 2: ......
Page 4: ...iv Reference Manual 00809 0200 4728 Rev RA Title Page April 2015 ...
Page 10: ...x Reference Manual 00809 0200 4728 Rev RA Table of Contents April 2015 Table of Contents ...
Page 180: ...Index 2 Reference Manual 00809 0200 4728 Rev RA Index April 2015 Index ...
Page 181: ......