Appendix B: Product Certifications
April 2015
127
Appendix B
Product Certifications
B.1
European Directive Information
A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The
most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com.
B.1.1
Ordinary Location Certification from FM Approvals
As standard, the transmitter has been examined and tested to determine that the design meets
the basic electrical, mechanical, and fire protection requirements by a nationally recognized
test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health
Administration (OSHA).
B.1.2
Installing Equipment in North America
The US National Electrical Code (NEC) and the Canadian Electrical Code (CEC) permit the use of
Division marked equipment in Zones and Zone marked equipment in Divisions. The markings
must be suitable for the area classification, gas, and temperature class. This information is
clearly defined in the respective codes.
B.1.3
Hazardous Locations Certifications
USA
E5
USA Explosionproof, Non-Incendive, Dust-Ignitionproof
Certificate: [XP & DIP]: 3006278; [NI]: 3008880 & 3044581
Standards: FM Class 3600: 2011, FM Class 3615: 2006, FM Class 3616: 2011, FM Class
3810: 2005, NEMA-250: 250: 2003, ANSI/IEC 60529: 2004
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II / III, GP E, F, G; (-50°C
≤
Ta
≤
+85°C); Type 4X;
See I5 description for Non-Incendive markings
I5
USA Intrinsic Safety and Non-Incendive
Certificate: 3008880 [Headmount Fieldbus/Profibus, Railmount HART]
Standards: FM Class 3600: 1998, FM Class 3610: 2010, FM Class 3611: 2004, FM Class
3810: 2005, NEMA - 250: 1991.
Markings: IS CL I / II / III, DIV I, GP A, B, C, D, E, F, G; NI CL I, DIV 2, GP A, B, C, D.
Special Conditions for Safe Use (X):
1.
When no enclosure option is selected, the Model 644 Temperature Transmitter shall be
installed in an enclosure meeting the requirements of ANSI/ISA S82.01 and S82.03 or
other applicable ordinary location standards.
2.
Option code K5 is only applicable with Rosemount J5 Universal Head (M20 x 1.5) or
Rosemount J6 Universal Head (
1
/
2
-14 NPT) enclosure.
3.
An enclosure options must be selected to maintain a Type 4X rating.