Section 3. Installation
Extension Pipe for Minimum Distance.
The radar level gauge should be placed so that there is always 800 mm or
more between the flange and the maximum product level. If the tank is filled
above the maximum product level, an extension pipe can be mounted to raise
the radar level gauge so that it measures correctly all the way up to the
maximum level, see Figure 3-16.
Figure 3-16. Rosemount 5900
with extension pipe
Minimum 800 mm
to product surface