Reference Manual
300520EN, Rev AA
November 2009
Rosemount 5900 Series
3-44
Section 3. Installation
3.4.10 Terminal Blocks
Figure 3-19. Rosemount 5900
terminal compartment
Table 3-7. Standard terminal
block connections for the 5900
The X1 terminal is connected to the intrinsically safe Raptor Tankbus.
A jumper on the X2 terminal enables the built-in termination. The termination
should be used if the Rosemount 5900 gauge is installed at the end of a
Tankbus network. See “The Raptor Tankbus” on page 3-41 for more
information on how to terminate the Raptor Tankbus.
The X3 terminal is used for connecting the cable shield in order to enable a
continuous shield throughout the Tankbus network.
The X4 terminal can be used for “daisy-chain” connection to other Raptor
devices such as the 2240 tank temperature multiplexer, or the 2230 tank
display unit, see also Figure 3-22 on page 3-47.
Ground terminals, internal
Test terminals
Test terminals
Connection
Standard
X1: Tankbus in
Intrinsically safe Tankbus input, power and communication
X2: Terminate on
The integrated line terminator is connected over the Tankbus
when a jumper is placed in the terminal block
X3: Shield loop through
Cable shield daisy-chain connector (not grounded)
X4: Tankbus out
Tankbus output connected to X1 for optional daisy-chain
connection to other devices
Test terminals
Test terminals for temporary connection of a handheld
communicator such as the Rosemount 375 Field Communcator