Reference Manual
300520EN, Rev AA
November 2009
Rosemount 5900 Series
4-10
Section 4. Configuration
4.5.2
LPG
Configuration
In the following description it is assumed that the Rosemount 5900 LPG
gauge is installed on the tank, and that a basic configuration is done as
described in the
Rex II System Configuration Manual
(Document no.
300510EN). Then it needs to be configured for LPG measurements. Do the
following:
1. Ensure that the tank is empty.
2. Check that the ball valve (optional) on the gauge is open.
In the TankMaster WinSetup work space choose the
Logical View
tab. Select
the icon that represents the radar level gauge, click the right mouse button
and choose
LPG Setup
.
3. In the
LPG Setup
window click the
Correction
button.
Choose
Air Correction Only
from the list of correction methods and click the
OK button.
NOTE!
The Air Correction Only option shall only be used when the tank atmosphere
contains air and no other gases.
When the LPG configuration is finished, the correction method needs to be
changed to a correction method that applies to the particular type of product
that is used.
Correction
Preliminary