IO-Link does not save tank adjustment information. After the level transmitter fails,
perform another tank adjustment. The level transmitter reverts to the cyclical
process data transmission after performing a tank adjustment successfully.
After a factory reset, the device reboots and the factory settings are restored.
3.6.2
Unit locking and data storage
The IO-Link master saves all parameters of the connected transmitter (except tank
adjustment) if configured in the master (data storage). When a transmitter is replaced by a
transmitter of the same type, the parameters of the old transmitter are automatically
written to the new transmitter if configured in the master and if the transmitter allows
this.
For safety reasons, the level transmitter can refuse the parameter download.
Factory default setting: Open
Data storage
•
Open: the transmitter allows parameter download from the master
•
Locked: the transmitter refuses parameter download from the master
Quick Start Guide
Operation
00825-0100-4326
January 2019
Quick Start Guide
41
Summary of Contents for Rosemount 326L
Page 1: ...Quick Start Guide 00825 0100 4326 Rev 01 January 2019 Rosemount 326L Level Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4326 4 Quick Start Guide ...
Page 12: ...Introduction Quick Start Guide January 2019 00825 0100 4326 12 Quick Start Guide ...
Page 24: ...Installation Quick Start Guide January 2019 00825 0100 4326 24 Quick Start Guide ...
Page 42: ...Operation Quick Start Guide January 2019 00825 0100 4326 42 Quick Start Guide ...
Page 48: ...Setting ranges Quick Start Guide January 2019 00825 0100 4326 48 Quick Start Guide ...
Page 50: ...Product certifications Quick Start Guide January 2019 00825 0100 4326 50 Quick Start Guide ...