Note
Use the
Hnc
switching function if the switching output is used as an overflow
prevention. The principle of normally closed operation ensures that the level
transmitter also detects wire breaks or cable breaks.
Set switching limits (hysteresis)
Use these steps to set the hysteresis limits for the switching output.
Procedure
1. Ensure that the function
Hno
or
Hnc
is set for
ou1
or
ou2
.
2. Select
SP1
or
SP2
then set the value at which the output is set.
3. Select
rP1
or
rP2
then set the value at which the output is reset.
Note
rPx
is always smaller than
SPx
. The level transmitter accepts only values which are
lower than the value for
SPx
. If
SPx
changes,
rPx
also changes provided that the
lower end of the setting range is not reached.
Set switching limits (window)
Use these steps to set the limits for the window switching output.
Procedure
1. Ensure that the function
Fno
or
Fnc
is set for
ou1
or
ou2
.
2. Select
FH1
or
FH2
then set the upper limit of the acceptable range.
3. Select
FL1
or
FL2
then set the lower limit of the acceptable range.
Note
FLx
is always lower than
FHx
. The level transmitter accepts only values which are
lower than the value for
FHx
. If
FHx
changes,
FLx
also changes provided that the
lower end of the setting range is not reached.
Set switch-on delay for switching outputs
Follow these steps to set the switch-on delay for switching outputs.
Procedure
1. Select
dS1
or
dS2
from the menu.
2. Set the value between 0.0 and 60 seconds.
Note
The switch-on delay reacts according to VDMA. According to VDMA, the switch-on
delay always effects SP and the switch-off delay always effects rP irrespective of
whether the level transmitter uses the normally open or normally closed function.
Quick Start Guide
Operation
00825-0100-4326
January 2019
Quick Start Guide
33
Summary of Contents for Rosemount 326L
Page 1: ...Quick Start Guide 00825 0100 4326 Rev 01 January 2019 Rosemount 326L Level Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4326 4 Quick Start Guide ...
Page 12: ...Introduction Quick Start Guide January 2019 00825 0100 4326 12 Quick Start Guide ...
Page 24: ...Installation Quick Start Guide January 2019 00825 0100 4326 24 Quick Start Guide ...
Page 42: ...Operation Quick Start Guide January 2019 00825 0100 4326 42 Quick Start Guide ...
Page 48: ...Setting ranges Quick Start Guide January 2019 00825 0100 4326 48 Quick Start Guide ...
Page 50: ...Product certifications Quick Start Guide January 2019 00825 0100 4326 50 Quick Start Guide ...