Highly absorbing surfaces (foam)
•
Intensely bubbling surfaces
•
Media which are very inhomogeneous, separate from each other thus forming
separation layers (oil layer on water)
To prevent this, follow these guidelines:
•
Check the function by performing an application test.
•
Install the level transmitter in a steady environment.
In case of signal loss, the level transmitter displays SEnS and switches the outputs to a
defined state. See
Output response in different operating states
for more information.
The level transmitter is not suitable for:
•
Bulk materials like plastic granulates and media with a very low dielectric constant like
oils.
•
Applications where the probe is subjected to permanent and high mechanical stress.
For example, fast moving viscous medium or fast flowing medium.
Use the level transmitter preferably with metal tanks. When used with plastic tanks,
deterioration caused by electromagnetic interference might occur (noise immunity to
EN61000-6-2).
1.3
Measuring principle
The level transmitter uses guided wave radar to measure media level. It emits
electromagnetic pulses every nanosecond to measure the level.
Figure 1-1: Transmitting Pulses
Introduction
Quick Start Guide
January 2019
00825-0100-4326
6
Quick Start Guide
Summary of Contents for Rosemount 326L
Page 1: ...Quick Start Guide 00825 0100 4326 Rev 01 January 2019 Rosemount 326L Level Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4326 4 Quick Start Guide ...
Page 12: ...Introduction Quick Start Guide January 2019 00825 0100 4326 12 Quick Start Guide ...
Page 24: ...Installation Quick Start Guide January 2019 00825 0100 4326 24 Quick Start Guide ...
Page 42: ...Operation Quick Start Guide January 2019 00825 0100 4326 42 Quick Start Guide ...
Page 48: ...Setting ranges Quick Start Guide January 2019 00825 0100 4326 48 Quick Start Guide ...
Page 50: ...Product certifications Quick Start Guide January 2019 00825 0100 4326 50 Quick Start Guide ...