61
Reference Manual
00809-0700-4001, Rev AA
Troubleshooting
May 2017
Troubleshooting
6.4
Disassembly procedures
Do not remove the instrument cover in explosive atmospheres when the circuit is live.
6.4.1
Removing from service
1. Follow all plant safety rules and procedures.
2. Power down device.
3. Isolate and vent the process from the transmitter before removing the transmitter from service.
4. Remove all electrical leads and disconnect conduit.
5. Remove the transmitter from the process connection.
a. The Rosemount 3051P Transmitter is attached to the process by a single hex nut process
connection. Loosen the hex nut to separate the transmitter from the process.
Note
Do not wrench on neck of transmitter. See warning in
“Inline process connection” on page 33
6. Do not scratch, puncture, or depress the isolating diaphragms.
7. Clean isolating diaphragms with a soft rag and a mild cleaning solution, and rinse with clear water.
Analog
Output
Fixed
ANLOG
FIXED
ANALOG
FIXED
The analog output is fixed
and does not represent
the process
measurement. This may
be caused by other
conditions in the device,
or because the device has
been set to loop test or
multidrop mode.
1. Take action on any other notifications from the device.
2. If the device is in loop test, and should no longer be,
disable or momentarily remove power.
3. If the device is in multidrop mode and should not be,
re-enable loop current by setting the polling address to
0.
Simulation
Active
[none]
[none]
The device is in simulation
mode and may not be
reporting actual
information.
1. Verify that simulation is no longer required.
2. Disable simulation mode in service tools.
3. Perform a Device Reset.
Analog
Output
Saturated
ANLOG
SAT
ANALOG
SAT
The analog output is
saturated either high or
low due to the pressure
either above or below the
range values.
1. Check the pressure applied to ensure it is between the
4–20mA points.
2. Check the transmitter pressure connection to make sure
it is not plugged or isolating diaphragms are not
damaged.
3. Replace the pressure transmitter.
Table 6-4. Status: Advisory
Alert name
LCD
display
screen
LOI
screen
Problem
Recommended action
Summary of Contents for Rosemount 3051P
Page 2: ......
Page 8: ...6 Reference Manual 00809 0700 4001 Rev AA Contents May 2017 Contents ...
Page 12: ...2 Reference Manual 00809 0700 4001 Rev AA Introduction May 2017 Introduction ...
Page 36: ...26 Reference Manual 00809 0700 4001 Rev AA Configuration May 2017 Configuration ...
Page 74: ...64 Reference Manual 00809 0700 4001 Rev AA Troubleshooting May 2017 Troubleshooting ...
Page 109: ......