22
Reference Manual
00809-0700-4001, Rev AA
Configuration
May 2017
Configuration
Using an analog loop test using AMS Device Manager
1. Right click on the device and, within the
Methods
drop down menu, move cursor over
Diagnostics and
Test
. In the
Diagnostics and Test
drop down menu select
Loop Test
.
2. Select
Next
after setting the control loop to manual.
3. Follow Screen prompts to perform a Loop Test.
4. Select
Finish
to acknowledge the method is complete.
Using an analog loop test using a LOI
To perform an analog loop test using the LOI, the 4 mA, 20 mA, and custom mA point may be set
manually. Reference
for instructions on how to perform a transmitter loop test using an LOI.
Figure 2-16. Performing an Analog Loop Test Using an LOI
2.11.3
Simulate device variables
It is possible to temporarily set the Pressure, Sensor Temperature, or Scaled Variable to a user-defined
fixed value for testing purposes. Once the simulated variable method is left, the process variable will be
automatically returned to a live measurement. Simulate device variables is only available in HART
Revision 7 mode.
Simulate digital signal with a Field Communicator
Simulate digital signal with AMS Device Manager
1. Right click on the device and select
Service Tools
.
2. Select
Simulate.
3. Under
Device Variables
select a digital value to simulate.
a. Pressure
b. Sensor Temperature
c. Scaled Variable
4. Follow the screen prompts to simulate selected digital value.
From the
HOME
screen, enter the Fast Key sequence
Device Dashboard Fast Keys
3, 5
LOOP TEST
SET 4MA
SET 20MA
SET CUSTOM
END LOOP TEST
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Summary of Contents for Rosemount 3051P
Page 2: ......
Page 8: ...6 Reference Manual 00809 0700 4001 Rev AA Contents May 2017 Contents ...
Page 12: ...2 Reference Manual 00809 0700 4001 Rev AA Introduction May 2017 Introduction ...
Page 36: ...26 Reference Manual 00809 0700 4001 Rev AA Configuration May 2017 Configuration ...
Page 74: ...64 Reference Manual 00809 0700 4001 Rev AA Troubleshooting May 2017 Troubleshooting ...
Page 109: ......