Reference Manual
00809-0700-4001, Rev AA
Configuration
May 2017
Configuration
Figure 2-6. LOI Configuration Buttons
A. Internal configuration buttons
B. External configuration buttons
Table 2-2. LOI Button Operation
2.6.3
Setting the loop to manual
Whenever sending or requesting data that would disrupt the loop or change the output of the
transmitter, set the process application loop to manual control. The Field Communicator, AMS Device
Manager, or the LOI will prompt you to set the loop to manual when necessary. The prompt is only a
reminder; acknowledging this prompt does not set the loop to manual. It is necessary to set the loop to
manual control as a separate operation.
2.7
Verify configuration
It is recommended that various configuration parameters are verified prior to installation into the
process. The various parameters are detailed out for each configuration tool. Depending on what
configuration tool(s) are available follow the steps listed relevant to each tool.
2.7.1
Verifying configuration with Field Communicator
Configuration parameters listed in
are to be reviewed prior to transmitter installation. A Full list
of configuration parameters that can be reviewed and configured using a Field Communicator are
located in
Appendix C: Field Communicator Menu Trees and Fast Keys
Fast key sequences for the latest DD are shown in
. For Fast Key sequences for legacy DD's
contact your local Emerson Representative.
Button
Left
No
SCROLL
Right
Yes
ENTER
B
A
Summary of Contents for Rosemount 3051P
Page 2: ......
Page 8: ...6 Reference Manual 00809 0700 4001 Rev AA Contents May 2017 Contents ...
Page 12: ...2 Reference Manual 00809 0700 4001 Rev AA Introduction May 2017 Introduction ...
Page 36: ...26 Reference Manual 00809 0700 4001 Rev AA Configuration May 2017 Configuration ...
Page 74: ...64 Reference Manual 00809 0700 4001 Rev AA Troubleshooting May 2017 Troubleshooting ...
Page 109: ......