Reference Manual
00809-0100-4108, Rev CA
Hardware Installation
May 2017
Hardware Installation
Vent all gas from liquid piping legs.
When purging, make the purge connection close to the process taps and purge through equal lengths
of the same size pipe. Avoid purging through the transmitter.
Keep corrosive or hot (above 250 °F [121 °C]) process material out of direct contact with the sensor
module and flanges.
Prevent sediment deposits in the impulse piping.
Avoid conditions that might allow process fluid to freeze within the process flange.
3.4.3
Inline process connection
Inline gage transmitter orientation
The low side pressure port on the inline gage transmitter is located in the neck of the transmitter, behind
the housing. The vent path is 360 degrees around the transmitter between the housing and sensor (See
).
Keep the vent path free of any obstruction, such as paint, dust, and lubrication by mounting the
transmitter so the process can drain away.
Figure 3-6. In-Line Gage Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
Interfering or blocking the atmospheric reference port will cause the transmitter to output erroneous
pressure values.
Do not apply torque directly to the sensor module. Rotation between the sensor module and the
process connection can damage the electronics. To avoid damage, apply torque only to the hex-shaped
process connection.
A. Sensor module
B. Process connection
A
B
Summary of Contents for Rosemount 3051P
Page 2: ......
Page 8: ...6 Reference Manual 00809 0700 4001 Rev AA Contents May 2017 Contents ...
Page 12: ...2 Reference Manual 00809 0700 4001 Rev AA Introduction May 2017 Introduction ...
Page 36: ...26 Reference Manual 00809 0700 4001 Rev AA Configuration May 2017 Configuration ...
Page 74: ...64 Reference Manual 00809 0700 4001 Rev AA Troubleshooting May 2017 Troubleshooting ...
Page 109: ......