HART Communicator
October 2016
Reference Manual
00809-0100-4808, Rev DA
68
HART Communicator
Download data from
configuration memory to
device
Select the
SEND
softkey to transfer information from the communicator
memory to the device.
Exceed field width
Indicates the field width for the current arithmetic variable exceeds the
device-specified description edit format.
Exceed precision
Indicates the precision for the current arithmetic variable exceeds the
device-specified description edit format.
Ignore next 50 occurrences
of status?
Select
YES
to ignore the next 50 occurrences of device status, or select
NO
to
display every occurrence.
Illegal character
An invalid character for the variable type was entered.
Illegal date
The day portion of the date is invalid.
Illegal month
The month portion of the date is invalid.
Illegal year
The year portion of the date is invalid.
Incompatible CPU board and
module ON
Return to Rosemount Nuclear Instruments, Inc. for repair.
Incomplete exponent
The exponent of a scientific notation floating point variable is incomplete.
Incomplete field
The value entered is not complete for the variable type.
Looking for a device
Polling for multidropped devices at addresses 1–15.
Local buttons operator error
ON
Illegal pressure applied during zero or span operation. Repeat the process after
verifying the correct pressures.
Mark as read only variable on
hotkey menu?
Asks whether the user should be allowed to edit the variable from the hotkey
menu if the item being added to the hotkey menu is a variable.
Module EEPROM write
failure ON
Message sent to the module from the HART signal failed. Return to Rosemount
Nuclear Instruments, Inc. for repair.
No device configuration in
configuration memory
There is no configuration saved in memory available to re-configure offline or
transfer to a device.
No Device Found
Poll of address zero fails to find a device, or poll of all addresses fails to find a
device if auto-poll is enabled.
No hotkey menu available
for this device.
There is no menu named “hotkey” defined in the device description for this
device.
No pressure updates ON
No pressure updates being received from the sensor module. Verify the sensor
module ribbon cable is attached correctly. Return to Rosemount Nuclear
Instruments, Inc. for repair.
No offline devices available.
There are no device descriptions available to be used to configure a device
offline.
No simulation devices
available.
There are no device descriptions available to simulate a device.
No temperature
updates ON
No temperature updates being received from the sensor module. Verify the
sensor module ribbon cable is attached correctly. Return to Rosemount Nuclear
Instruments, Inc. for repair.
No UPLOAD_VARIABLES in
ddl for this device
There is no menu named “upload_variables” defined in the device description
for this device. This menu is required for offline configuration.
No Valid Items
The selected menu or edit display contains no valid items.
OFF KEY DISABLED
Appears when user attempts to turn the HC off before sending modified data or
before completing a method.
Online device disconnected
with unsent data. RETRY or
OK to lose data.
There is unsent data for a previously connected device. Select
RETRY
to send
data, or select
OK
to disconnect and lose unsent data.
Message
Description