28
Reference Manual
00809-0100-4808, Rev DA
Installation
October 2016
Installation
3.4.2
Steam service
For steam service, do not blow down impulse piping through the transmitter. Flush the lines with the
blocking valves closed and refill the lines with water before resuming measurement.
3.4.3
Side mounting
When the transmitter is mounted on its side, position the coplanar process flange to ensure proper
venting or draining. Keep drain/vent connections on the bottom for gas service and on the top for liquid
service.
3.4.4
Independent seals
The Rosemount 3051N Transmitter incorporates two independent seals between the process
connection and the conduit connection.
Figure 3-2. Coplanar Flange Mounting Configurations with Optional Bracket (Code B4) for Panel
Mounting
A.
5
/
16
bolts for panel mounting (not supplied)
B.
3
/
8
-16 x 1
1
/
4
bolts for mounting to transmitter
Note: Dimensions are nominal in inches (millimeters).
B
A
2.81
(71)
3.4
(85)