background image

7

Type OSE

•  Precaution should be taken when removing or replacing 

the valve plug to avoid damaging the segments

•  Lubricate screws before tightening

•  Lubricate O-rings (silicone grease) except for the valve 

plug O-ring

•  Lightly lubricate the stem (silicone grease)

•  Lubricate the release relay mechanism (yoke and bolt) 

(molybdenum graphite grease)

•  Lubricate the BMS spring (molybdenum graphite grease)

A special tool is required when installing a new ori

fi

 ce

Table 7.

 Troubleshooting for Type OSE Slam-Shut Valve

Table 5.

 Torques for Connecting Part Screw 

(key 10, Fig. 7)

DN

Dimensions

Spanner (inches)

Torque

(N.m)

25

9/16-12 

X

 1 3/4

13/16’’

110

50

1/2-13 

X

 1 1/2

3/4’’

110

80

5/8-11 

X

 1 3/4

15/16’’

175

100

3/4-10 

X

 2 1/4

1’’1/8

260

150

1-8 

X

 2 3/4

1’’1/2

510

C58a

Table 6.

 Torques for Bypass (key 1. Fig. 7)

DN

Torque (N.m)

25

14

50

14

80

20

100

24

150

24

C58b

C58c

Key

Torque (N.m)

9

15

14

Table 4.

 Torques (key 9 & 14, Fig. 7)

SYMPTOMS

CAUSE

ACTIONS

If the valve will not close

Operating fault

Check the release relay

Check the valve plug
or contact after-sales

If the valve closes

Operating correctly

Observe the evolution of the outlet pressure

(check tightness)

If the outlet pressure in the slam shut is 

decreases

External leak

Locate and seal the leak

or contact after-sales

If the outlet pressure in the slam shut is 

constant

Bleed off the outlet side of the regulator

Observe the evolution of the outlet pressure

(check tightness)

If the outlet pressure increases

Internal leak

Check the slam shut valve plug

Check the ori

fi

 ce

Check the bypass

or contact after-sales

Key

Description

DN 25

DN 50

DN 80

DN 100

DN 150

1

Bypasse

180977

2

Valve plug O-ring

400257

400263

400258

400260

400261

3

Segments

401950

401951

401952

401953

401954

4

O-ring

400298

400295

400297

400296

19B0359X12

5

O-ring

400009

400024

400259

400045

400262

Packing gland “Kit” 

197395

Set of O-rings*

197447

197448

197449

197450

197451

Spare parts kit**

197452

197453

197454

197455

197456

Release Relay Type OS2

See D103683X012 manual

(*) Set of O-rings and segments including O-rings key 2, 3, 4, 5 

(**) Spare-parts kit including set of O-rings, bypass (key 1) and bypass disassembly spanner

Table 8.

 Spare Parts for Type OSE Slam-Shut Valve

SPARE PARTS

Summary of Contents for OSE Series

Page 1: ...eter Tube interior Ø 8 10 mm Safety contact See D103683X012 manual INTRODUCTION Scope of Manual This manual provides installation start up maintenance and parts ordering information for the Type OSE Slam Shut Valve Information on other equipment used with this slam shut valve is found in separate manuals Product Description The OSE Slam Shut Valve protects transmission and distribution networks or...

Page 2: ...ay travel mm 35 35 50 50 50 C50 Table 2 Flow Coefficient ΔP max Relay travel Figure 2 Label for Type OSE Slam Shut Valve OPERATING PRESSURE Body valve plug PS 100 bar maxi Associated BMS 1 according to size PSD 10 à 100 bar Maximum Inlet Pressure Pumax 100 bar Type DS Differential strength 2 OPERATING TEMPERATURE 3 TS 20 60 C 30 71 C SLAM SHUT Sizes available DN 25 50 80 100 150 Norm EN 14382 Oper...

Page 3: ...0 62 334 220 124 17 50 20 150 254 76 346 220 152 26 50 300 267 83 346 220 165 29 100 600 287 83 346 220 165 32 80 20 150 298 95 380 220 190 43 50 300 318 105 380 220 210 48 100 600 337 105 380 220 210 55 100 20 150 353 114 420 220 229 74 50 300 368 127 420 220 154 82 100 600 394 137 420 220 273 98 150 20 150 451 140 424 220 357 150 50 300 473 159 424 220 357 166 100 600 508 178 424 220 357 202 C53...

Page 4: ...ciple of Operation The slam shut valve is installed on the inlet side of the regulator on the horizontal pipeline The mechanism box should be situated on top see above schematic or on top for versions DN 25 50 80 Installation according to EN12186 is recommended Install according to direction of the fluid flow see arrow When assembling with adjacent elements care must be taken not to create pressur...

Page 5: ...be checked periodically COMMISSIONING WARNING All interventions on the equipment should only be performed by qualified and trained personnel Preliminary verifications Start up positions Inlet and outlet valves Closed Verify absence of pressure between inlet and outlet valves Slam shut valve plug Closed Impulse isolation valve Closed Impulse atmospheric valve Open Setpoint Verification Using the at...

Page 6: ...frequency Every 4 to 6 years or less depending on operating conditions In the case of BMS 162 or 071 it is highly recommended to check the condition of the diaphragm once yearly Verification Condition of O rings diaphragm and lubrication Replacement O rings diaphragm Tools Spanners 10 13 six sided wrench 6 Spanners According to DN size Francel spanner ref 197125 bypass and pin disassembly Valve pl...

Page 7: ...k the valve plug or contact after sales If the valve closes Operating correctly Observe the evolution of the outlet pressure check tightness If the outlet pressure in the slam shut is decreases External leak Locate and seal the leak or contact after sales If the outlet pressure in the slam shut is constant Bleed off the outlet side of the regulator Observe the evolution of the outlet pressure chec...

Page 8: ...972 548 3574 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9000 Europe Bologna 40013 Italy Tel 39 051 419 0611 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 For further information visit www emersonprocess com regulators Natural Gas Technologies Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1...

Reviews: