Type OSE

Safety contact: see D103683X012 manual

C54

Pu

Pd

REGULATOR

D

E

IS

4 D

Figure 5.

 Type OSE Slam-Shut Valve Installation Schematic

Verify that the limits of utilization correspond 
to the appropriate operating conditions.

Verify that the safety manometric box (BMS) 
and spring correspond to the appropriate 
operating conditions on the outlet side of the 
regulator.

The equipment should not receive any type 
of shock, especially the release relay.

The user should verify or carry out a 
protection adapted to the environment.

Fire, seismic and lightening are not taken 
into consideration for standard regulators. 
If required, a special product selection and/
or speci

fi

 c calculations may be supplied 

according to speci

fi

 c requirements.

If the slam-shut is classi

fi

 ed under operating 

class B the BMS diaphragm should be 
checked periodically.

COMMISSIONING

!

WARNING

All interventions on the equipment should 
only be performed by quali

fi

 ed and 

trained personnel.

Preliminary veri

fi

 cations

Start-up positions

•  Inlet and outlet valves

 

 Closed

Verify absence of pressure between inlet and outlet valves

•  Slam-shut valve plug

 

 Closed

•  Impulse isolation valve

 

 Closed

•  Impulse atmospheric valve

 

 Open

Setpoint Veri

fi

 cation

Using the atmospheric valve, inject a pressure equal to the 
pressure foreseen for the regulator

• 1

st

 release relay stage

 

 

Set (Stage 1)

TRIGGERED POSITION

TRAVEL 

STOP

TRAVEL 

STOP

TRAVEL 

STOP

1

2

3

C59

Figure 6.

 Setpoint Veri

fi

 cation

STAGES 2 & 3

STAGE 1

•  Slam shut valve

 

 

Open (Stages 2 & 3)

 

 Progressively increase the pressure to reach tripping

 

 Adjust setting if necessary (D103683X012 manual)

Note the set point value on the equipment or mark it in a 
commissioning document.

Positions before Commissioning

•  Impulse isolation valve

 

 Open

•  Impulse atmospheric valve

 

 Closed

•  Slam shut valve plug

 

 Closed

The equipment is ready for commissioning

Summary of Contents for OSE Series

Page 1: ...eter Tube interior Ø 8 10 mm Safety contact See D103683X012 manual INTRODUCTION Scope of Manual This manual provides installation start up maintenance and parts ordering information for the Type OSE Slam Shut Valve Information on other equipment used with this slam shut valve is found in separate manuals Product Description The OSE Slam Shut Valve protects transmission and distribution networks or...

Page 2: ...ay travel mm 35 35 50 50 50 C50 Table 2 Flow Coefficient ΔP max Relay travel Figure 2 Label for Type OSE Slam Shut Valve OPERATING PRESSURE Body valve plug PS 100 bar maxi Associated BMS 1 according to size PSD 10 à 100 bar Maximum Inlet Pressure Pumax 100 bar Type DS Differential strength 2 OPERATING TEMPERATURE 3 TS 20 60 C 30 71 C SLAM SHUT Sizes available DN 25 50 80 100 150 Norm EN 14382 Oper...

Page 3: ...0 62 334 220 124 17 50 20 150 254 76 346 220 152 26 50 300 267 83 346 220 165 29 100 600 287 83 346 220 165 32 80 20 150 298 95 380 220 190 43 50 300 318 105 380 220 210 48 100 600 337 105 380 220 210 55 100 20 150 353 114 420 220 229 74 50 300 368 127 420 220 154 82 100 600 394 137 420 220 273 98 150 20 150 451 140 424 220 357 150 50 300 473 159 424 220 357 166 100 600 508 178 424 220 357 202 C53...

Page 4: ...ciple of Operation The slam shut valve is installed on the inlet side of the regulator on the horizontal pipeline The mechanism box should be situated on top see above schematic or on top for versions DN 25 50 80 Installation according to EN12186 is recommended Install according to direction of the fluid flow see arrow When assembling with adjacent elements care must be taken not to create pressur...

Page 5: ...be checked periodically COMMISSIONING WARNING All interventions on the equipment should only be performed by qualified and trained personnel Preliminary verifications Start up positions Inlet and outlet valves Closed Verify absence of pressure between inlet and outlet valves Slam shut valve plug Closed Impulse isolation valve Closed Impulse atmospheric valve Open Setpoint Verification Using the at...

Page 6: ...frequency Every 4 to 6 years or less depending on operating conditions In the case of BMS 162 or 071 it is highly recommended to check the condition of the diaphragm once yearly Verification Condition of O rings diaphragm and lubrication Replacement O rings diaphragm Tools Spanners 10 13 six sided wrench 6 Spanners According to DN size Francel spanner ref 197125 bypass and pin disassembly Valve pl...

Page 7: ...k the valve plug or contact after sales If the valve closes Operating correctly Observe the evolution of the outlet pressure check tightness If the outlet pressure in the slam shut is decreases External leak Locate and seal the leak or contact after sales If the outlet pressure in the slam shut is constant Bleed off the outlet side of the regulator Observe the evolution of the outlet pressure chec...

Page 8: ...972 548 3574 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9000 Europe Bologna 40013 Italy Tel 39 051 419 0611 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 For further information visit www emersonprocess com regulators Natural Gas Technologies Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1...

Reviews: