5
Type OSE
Safety contact: see D103683X012 manual
C54
Pu
Pd
REGULATOR
D
E
IS
4 D
Figure 5.
Type OSE Slam-Shut Valve Installation Schematic
Verify that the limits of utilization correspond
to the appropriate operating conditions.
Verify that the safety manometric box (BMS)
and spring correspond to the appropriate
operating conditions on the outlet side of the
regulator.
The equipment should not receive any type
of shock, especially the release relay.
The user should verify or carry out a
protection adapted to the environment.
Fire, seismic and lightening are not taken
into consideration for standard regulators.
If required, a special product selection and/
or speci
fi
c calculations may be supplied
according to speci
fi
c requirements.
If the slam-shut is classi
fi
ed under operating
class B the BMS diaphragm should be
checked periodically.
COMMISSIONING
!
WARNING
All interventions on the equipment should
only be performed by quali
fi
ed and
trained personnel.
Preliminary veri
fi
cations
Start-up positions
• Inlet and outlet valves
→
Closed
Verify absence of pressure between inlet and outlet valves
• Slam-shut valve plug
→
Closed
• Impulse isolation valve
→
Closed
• Impulse atmospheric valve
→
Open
Setpoint Veri
fi
cation
Using the atmospheric valve, inject a pressure equal to the
pressure foreseen for the regulator
• 1
st
release relay stage
→
Set (Stage 1)
TRIGGERED POSITION
TRAVEL
STOP
TRAVEL
STOP
TRAVEL
STOP
1
2
3
C59
Figure 6.
Setpoint Veri
fi
cation
STAGES 2 & 3
STAGE 1
• Slam shut valve
→
Open (Stages 2 & 3)
→
Progressively increase the pressure to reach tripping
→
Adjust setting if necessary (D103683X012 manual)
Note the set point value on the equipment or mark it in a
commissioning document.
Positions before Commissioning
• Impulse isolation valve
→
Open
• Impulse atmospheric valve
→
Closed
• Slam shut valve plug
→
Closed
The equipment is ready for commissioning