Chapter 6 Use Of Monitoring Module M501D 91
4. There are two pages of ‘Settings’. Shift page by using ▼ or ▲, and select the parameter by using ▼ or ▲. Press
ENT to confirm.
As shown in the above figure, the parameters are classified into 6 categories by the monitoring module, including
alarm parameter, battery parameter, AC parameter, DC parameter, module parameter and system parameter.
The alarm parameters include three types: alarm level, alarm mode and alarm control, shown as follows:
Alarm Settings
Alarm Level
Alarm Control
Alarm Mode
The battery parameters include five types: basic parameters, LVD protection, charge management, battery test, and
temperature compensation coefficient. The setting interface is divided into two screens, as shown in the following:
Batt. Settings
Batt Selection
LVD Setting
Charge
Batt. Settings
Battery Test
Temp. Comp
6.7.2 Alarm Settings
The root screen of the setting interface is as follows:
Alarm Settings
Alarm Level
Alarm Control
Alarm Mode
There are 3 submenus. Use ▼ or ▲ to select one, and use ENT to confirm.
The three submenus are shown below:
Alarm Type:
Alarm Block
Lev.: Observation
Out Relay: NC
Alarm Mode:
Digital 1: High
Name DI: 1
Name Level: NA
Alarm Control
Voice Sign: On
Clear Hist: N
Block Alarm: N
Use ▼ or ▲ to select one page or one of the parameters, and ◄ or ► to select the parameter value. Press ENT to
confirm and save.
Description of alarm level parameter function and value
‘Alarm type’: To select different types of alarms. The alarm types are defined in the following table.
Table 1.1 Alarm type definition
No.
Alarm name
Alarm description
Default
alarm
level
Default
associated
relay
Associated
setting parameters
1
Alarm blocked
To block the alarms sent to the MC. It functions in
the EEM protocol
Observati
on alarm
N/A
Alarm blocked
2
Load bypass
disconnected
Overload, short circuit, manual disconnection or
alarm circuit fault
Critical
alarm
6
3
LVD1
Load disconnected
Manual control of load LVD
Critical
alarm
5
Load LVD enabled
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual