9.1.3
Junction box (Model JB-MPD)
Class I, Division 1, Groups B, C, and D Class I Zone 1, AEx d/Ex d IIB+H
2
T5
-50 °C ≤ Ta ≤ +85 °C
Type 4X, IP67
9.2
ATEX (-X model)
9.2.1
Transmitter
0575
II 2 G Ex d IIB+H
2
T5, IP65
-40 °C ≤ Ta ≤ +85 °C
Presafe 16 ATEX 8594X
9.2.2
APM Sensor
0575
II 2 G Ex d IIB+H
2
T5, IP65
-40 °C < Ta < +75 °C
SIRA 17ATEX1242X
Special conditions for safe use
1. The permanently connected cable needs appropriate protection of the free end of the
cable.
2. The parts of the bushing outside the flameproof enclosure shall be protected in
accordance with one of the types of protection listed in EN60079-0.
3. The electrical earth bonding of the equipment shall be ensured during installation.