7
Wire resistance table
Distance
Feet (Meters)
AWG #20
0.5 mm
2
AWG #18
0.8 mm
2
AWG #16
1.0 mm
2
AWG #14
2.0 mm
2
100 (30.5)
1.02
0.64
0.40
0.25
200 (61)
2.03
1.28
0.80
0.51
300 (91.4)
3.05
1.92
1.20
0.76
400 (121.9)
4.06
2.55
1.61
1.01
500 (152.4)
5.08
3.20
2.01
1.26
600 (182.9)
6.09
3.83
2.41
1.52
700 (213.4)
7.11
4.47
2.81
1.77
800 (243.8)
8.12
5.11
3.21
2.02
900 (274.3)
9.14
5.75
3.61
2.27
1000 (304.8)
10.20
6.39
4.02
2.53
1250 (381)
12.70
7.99
5.03
3.16
1500 (457.2)
15.20
9.58
6.02
3.79
1750 (533.4)
17.80
11.20
7.03
4.42
2000 (609.6)
20.30
12.80
8.03
5.05
2250 (685.8)
22.80
14.40
9.03
5.68
2500 (762)
25.40
16.00
10.00
6.31
3000 (914.4)
30.50
19.20
12.00
7.58
3500 (1066.8)
35.50
22.40
14.10
8.84
4000 (1219.2)
40.60
25.50
16.10
10.00
4500 (1371.6)
45.70
28.70
18.10
11.40
5000 (1524)
50.10
32.00
20.10
12.60
5500 (1676.4)
55.80
35.10
22.10
13.91
6000 (1828.8)
61.00
38.30
24.10
15.20
6500 (1981.2)
66.00
41.50
26.10
16.40
7000 (2133.6)
71.10
44.70
28.10
17.70
7500 (2286)
76.10
47.90
30.10
19.00
8000 (2438.4)
81.20
51.10
23.10
20.20
9000 (2743.2)
91.40
57.50
36.10
22.70
10000 (3048)
102.00
63.90
40.20
25.30
Resistance shown is one way. This figure must be doubled when determining closed loop
resistance.
Wire resistance table
41
Summary of Contents for Net Safety Millennium
Page 4: ......
Page 8: ...Contents iv ...
Page 14: ...Transmitter Dimensions Figure 2 3 Junction Box Sensor Dimensions Figure 2 4 Installation 6 ...
Page 34: ...Operation 26 ...
Page 42: ...Programming flowchart Figure 4 2 Programming 34 ...
Page 46: ...Maintenance 38 ...
Page 48: ...Electrostatic sensitive device 40 ...
Page 50: ...Wire resistance table 42 ...
Page 54: ...Specifications 46 ...
Page 60: ...Ordering information 52 ...
Page 61: ...Ordering information 53 ...
Page 62: ...Ordering information 54 ...
Page 63: ...Ordering information 55 ...