Transmitter Wiring
Table 2-3:
Terminal
Function/marking
1 (GND)
Earth ground
2
Vdc (+)
3
COM (-)
4
Sig A
5
Sig B
6
Not used
7
Not used
2.5.10
Wiring transmitter to control system
Connect the Millennium transmitter to the control system as shown in
Figure 2-11
.
Table 2-4
outlines the terminal marking and their purpose.
Transmitter connections
Table 2-4:
Marking
RST
+24V
COM
4-20
+VISO
Function
Remote reset
10.5-32 Vdc
Connection
Common / supply
ground
Current loop output
(mA)
+24 Vdc isolated
4-20 power
2.5.11
External ground
In order to ensure proper operation of the sensor, an external earth ground is
recommended. Net Safety recommends that the external ground be connected to the
grounding point on the enclosure. Refer to
Figure 2-13
for grounding connection location.
Installation
17