42 Chapter 5 UPS Operation Instructions
Liebert
®
ITA 5kVA And 6kVA UPS User Manual
CB1
CB2
SW
Figure 5-53 Configuration of the single UPS with external maintenance bypass
For the UPS system which requires the power distribution to be accomplished by user, if you need to isolate the UPS
from AC power, disconnect the external input MCB.
Warning
Cut off the maintenance power to prevent physical injury.
5.9 Auto Restart
Upon mains failure, the UPS supplies power to the load through battery until the battery power is depleted, and the
UPS will terminate output.
Meet the following conditions, the UPS will automatically restart and recover output power supply.
The mains restores after battery EOD;
The UPS EOD Auto Restart function is enabled.
Note
1. The UPS EOD Auto Restart function is enabled by default if there is no customized requirement.
2. If the Auto Restart function is not enabled, you can start the UPS manually by pressing the ON/SILENCE key.
5.10 UPS Monitoring
For the methods of the UPS background monitoring, refer to
SiteMonitor Monitoring Software User Manual