6 Chapter 1 Product Introduction
Liebert
®
ITA 5kVA And 6kVA UPS User Manual
1.5.6 Maintenance Bypass Mode
If maintenance and repair for UPS are needed, you can transfer the load to the Maintenance Bypass through
maintenance bypass MCB, and the power to the load is not interrupted. The maintenance bypass MCB is located on
the front panel of the POD, and the capacity meets the requirements of total load capacities. Refer to
Liebert
®
ITA
5kVA And 6kVA UPS Parallel Power Distribution Unit User Manual
for the detailed introductions of the POD.
Note
When the UPS has malfunctions and cannot working normally, please get in touch with the nearest Emerson branch office or local
service center. It is prohibited to repair the UPS by yourself, otherwise the personnel injury and damage to the equipment will
occur.
1.6 Specifications
The specifications are listed in Table 1-2.
Table 1-2 Specifications
5kVA 6kVA
Standard model
Long back-up model
Standard model
Long back-up model
Item
UHA1R-0050 UHA1R-0050L UHA1R-0060 UHA1R-0060L
Rated voltage
Single-phase: 220/230/240Vac, 3-phase: 380/400/416Vac
Voltage range
Single-phase: 176Vac ~ 276Vac, 3-phase: 305Vac ~ 478Vac, at full load
Single-phase: 120Vac ~ 176Vac, 3-phase: 210Vac ~ 305Vac, linear derating
Single-phase: 120Vac, 3-phase: 210Vac, at half load
Frequency
50Hz/60Hz ± 5Hz
Input
Power factor
Single-phase:
≥
0.99, 3-phase:
≥
0.95
Rated power
4.5kW
4.8kW
Voltage
220/230/240Vac ± 3%
Frequency
In Normal mode: the output tracks the bypass frequency when the bypass frequency is within
50Hz/60Hz ± 5Hz
Frequency track rate
0.2Hz/s (default), 1Hz/s
Power factor
0.9
0.8
Crest factor
3: 1
Voltage harmonic
distortion
≤
3% (linear load),
≤
5% (non-linear load)
Load regulation rate
2%
Dynamic response
recovery time
60ms
Overload capacity
105% ~ 125% rated load for 1min, 125% ~ 150% rated load for 100ms
Bypass voltage
120Vac ~ 253/265/276Vac
Output
Mains efficiency
91%
Type
Sealed, lead-acid, maintenance-free battery (12V/7Ah)
Cell No.
16 (12V/7Ah)
Depended on
external battery
capacity (the battery
capacity should be
bigger than 56Ah)
16 (12V/7Ah)
Depended on
external battery
capacity (the battery
capacity should be
bigger than 56Ah)
Rated voltage
192Vdc
Recharge duration
Four hours to 90%
rated capacity
Depended on
external battery
capacity
Four hours to 90%
rated capacity
Depended on
external battery
capacity
Battery
Charge current
2A
4A
2A
4A
Mains
←→
Battery
0ms
Transf
er time
Inverter
←→
Bypass
≤
4ms
Noise
≤
50dB
Panel display mode
LED/LCD (optional)
Safety CCEE
(GB4943-1995)/GB4943