Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
October 2020
31
Actuator Configuration
Section 6: Actuator Configuration
6.2.2
Close Limit Configuration by Position
Enter set up configuration:
•
Move switch SW4 to position 2
•
Move switch SW6 to position 1
•
Move switch SW3 to position ON
•
Confirm by pushing ENTER pushbutton SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
6.2.3
Close Limit Configuration
•
Move switch SW3 to position ON
•
Drive the actuator to the close position using the handwheel
•
Move switch SW4 to position 0
•
Move switch SW6 to position 0
•
Confirm by pushing ENTER pushbutton SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
6.2.4
Open Limit Configuration by Position
•
Move switch SW4 to position 3
•
Move switch SW6 to position 1
•
Move switch SW3 to position ON
•
Confirm by pushing ENTER pushbutton SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter