October 2020
Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
36
Actuator Configuration
Section 6: Actuator Configuration
6.2.13
Actuator Model Selection
The frames relevant to models 63/125 and 250/500 can be set to operate with a 63 Nm
or 125 Nm motor and a 250 Nm or 500 Nm motor respectively. The difference is based on
the technical characteristics of the electric motor itself.
Actuator model 63
•
Enter set up configuration: move switch SW3 to position ON (configuration function)
•
Move switch SW4 to position 9
•
Move switch SW6 to position 0
•
Confirm by pushing ENTER pushbutton, SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit set up configuration (move switch SW3 to position 1) or proceed with
the next parameter
Actuator model 125
•
Enter set up configuration: move switch SW3 to position ON (configuration function)
•
Move switch SW4 to position 9
•
Move switch SW6 to position 1
•
Confirm by pushing ENTER pushbutton SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit set up configuration (move switch SW3 to position 1) or proceed with
the next parameter
Actuator model 250
•
Enter set up configuration: move switch SW3 to position ON (configuration function)
•
Move switch SW4 to position 9
•
Move switch SW6 to position 0
•
Confirm by pushing ENTER pushbutton SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit set up configuration (move switch SW3 to position 1) or proceed with
the next parameter