FSD Configuration Screen
E2 Data Point Setup for FSD • 17
tor for
Property:
(CONTROL TEMP)
.
When setting up data points for multiple E2s at a
site, note that
F4: Lookup
will not allow you to select
data points from another (remote) E2 unless you are
running E2 firmware revision 2.69F01 or higher.
For E2 firmware prior to revision 2.69F01, data
points can be selected from a remote E2 by connect-
ing the data points to Global Data.
Ethernet peer communications is required for box-
to-box hookup. For more information, refer to
Sec-
tion 7,
E2 Ethernet Peer Communications
.
8. Go to the
Pts Names
tab and enter a name
for the data point (
Figure 6-4
).
A point name is the unique name given to the data
point (specified by the user) and will be displayed on
the FSD screen.
9. After entering the data point, enter a
unique name in the
Data Name
field on
this screen. If no name is assigned, the
data point will be displayed in the default
Controller:Application:Property
format.
Figure 6-3
- Example of Data Point(s) Setup in E2
NOTE: Colons “:” cannot be used in the text
you enter when naming the data point, as co-
lons are already used to separate each value.
NOTE: If a pointer is undefined in the E2
application, it will display as three dashes
(- - -) on the Facility Status Display screen.
Figure 6-4
- Entering a Data Point Name