12 • FSD Installation and Operation Manual
026-1400 Rev 3 22-MAR-2011
5.4.1.2.
Show Reset Advisories
This alarm setting enables you to display or hide
reset alarms on the FSD. Reset alarms are alarms that
have been forced to normal condition or “Reset-to-
Normal.” Enable the checkbox to show reset alarms
or uncheck to filter out.
5.4.1.3.
Display Asset/Alarm
This setting determines how advisory information
will display on the FSD main alarm screen (whether
alarm is displayed over asset or vice versa).
Alarm
de-
scribes the type of alarm that was generated, while
as-
set
details the source where the alarm occurred.
If the
Display Asset/Alarm
checkbox is un-
checked, the main alarm screen will display advisory
information in the normal order, that is,
alarm over
asset
. In
Figure 5-12
, the alarm name (“Failed Sensor
or Bad Wiring”) is displayed over the asset detail
(“E3.1 >> EC2 391 CC_001 >> TERM TEMP”).
If the checkbox is enabled, alarm information will
display in the reverse order (i.e.,
asset over alarm
).
Refer to
Figure 5-13
for a sample illustration.
5.4.1.4.
Show Notices
This notice setting determines whether the FSD
will display notices along with other types of adviso-
ries, or whether these notices will be filtered out of the
FSD. Enable this box to show Notices in the alarm
list, uncheck to filter out.
5.4.1.5.
Filter Advisories
This setting causes the FSD to display only advi-
sory information of points that are included in the
monitored data point list. Advisories that are outside
the monitored data point list will be excluded from the
display list. Enable the checkbox to filter advisories,
or uncheck to filter out.
5.4.1.6.
Sort Data Points
If this setting is enabled, it will cause points with
active advisory to display on top of the list of moni-
tored data points on the FSD.
5.4.1.7.
Audible Alarm
Audible Alarm will be active any time there is an
active alarm or a fail advisory displayed. The Audible
Alarm drop-down list allows you to configure the au-
dible alarm buzzer on the FSD with three settings:
Ex-
ternal
,
Internal
, and
None
.
•
External
is the default. This setting enables the
audible external horn connected to the relay
board as the alarm indicator.
•
Internal
enables the touch-screen beep as the
Figure 5-12
- Normal Setting - Alarm over Asset
Figure 5-13