46
I/O Configuration and Wiring
Figure 3-8
shows how to wire a digital output as a contact closure using the internal 24V
loop supply. The total current for all devices connected to a DO channel must not exceed
500 mA. For example, you could wire two devices in parallel, one with 200 mA, and
another with 300 mA. This figure shows a single device using 500 mA.
Figure 3-8: Digital Output (DO) Wiring – Contact Closure using 24V Loop Supply
1
500 mA load max field device