Service and Troubleshooting
71
DANGER
EXPLOSION HAZARD: BATTERIES MUST ONLY BE CHANGED IN AN AREA FREE OF
IGNITABLE CONCENTRATIONS.
Battery in Power Module:
1.
Remove the power module.
2.
Grasp the battery and pull it out of the power module.
3.
Safely dispose of the old battery according to local regulations.
4.
Slide the replacement battery in. The positive (+) side with the writing on it must
be facing downwards, towards the RTU when the power module is installed.
5.
Reinstall the power module.
Battery in CPU Module:
1.
Remove the battery access door at the bottom of the CPU module, and the door
magnet will pull out the battery. (If this doesn’t work, use your own external
magnet to pull out the battery.)
Figure 5-5: Removing the SRAM Battery
2.
Safely dispose of the old battery according to local regulations.
3.
Slide the replacement battery in. The positive (+) side with the label must be
facing to the right side of the RTU. Push the battery access door back on.
Figure 5-6: Replacing the SRAM Battery