Emerson FB3000 RTU Instruction Manual
D301851X012
May 2022
30
Installation
Figure 2-24: COM3 Configured as RS-485 (2-wire) and Connected to Multiple 4088B Transmitters
1
Enable AC termination using switches on last multi-dropped 4088B transmitter
2
RS-485 bus; twisted pair required
3
Up to ten 4088B transmitters allowed per port; FB3000 only provides power for a
maximum of four transmitters. Any other transmitters require an external power supply.
When communicating with more than six 4088Bs at 9600 baud, update times exceed once
a second.
4
Connect cable shields to suitable Instrument Earth connection point
Summary of Contents for FB3000
Page 7: ...FB3000 CSA Approval Information CD9411L Issued March 11 2021 CSA 5 ...
Page 8: ......
Page 12: ......
Page 46: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 34 Installation ...
Page 68: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 56 I O Configuration and Wiring ...
Page 72: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 60 Operation ...
Page 94: ......