I/O Configuration and Wiring
3.6.2
Software Configuration
Consult the FBxConnect online help for full details. What follows is an overview of the
steps:
1.
From the Configure tab in FBxConnect, click I/O Setup > HART.
2.
Select the HART channel you want to configure; there are four HART channels per
module.
3.
If this channel is an analog input, click the Configuration tab to configure the AI.
4.
Specify whether this is a Primary or Secondary HART Master in the HART Master
Type field.
5.
Enable the Termination Resistor if required.
6.
Choose the HART Comm Mode:
•
If you have a single HART device on the channel, select Point to Point
•
If multiple devices are multi-dropped on the channel, select Multidrop and
specify the Number of Devices.
7.
Click Save. If you chose Multidrop, the HART menu creates a button for each of the
devices.
8.
Click on the Device button to configure the HART device on this channel.