FB3000 - CSA Approval Information
CD9411L
Issued: March 11, 2021
CSA-3
12V
≤ V < 24V
21
10
10.5V
≤ V <
12V
18
8
Conditions of Use:
Wiring to or from this device, which either enters or leaves the user-provided enclosure, must
adhere to wiring methods suitable for Class I, Zone 2 and Division 2 Hazardous locations, as
appropriate for the installation and is subject to the acceptance of CSA or the inspection authority
having jurisdiction.
Install this device in a user-provided enclosure that provides a minimum entry protection of IP 54,
in accordance with IEC 60079-0:11.
Install the racks in a left to right horizontal direction (wall mount on DIN-rails) inside of the end user
system enclosure. Never mount the racks in a vertical stacked direction
When using DIN-rail mounting as the method of installation for the extended backplane
configuration, use DIN-rail end brackets at the two ends of the extended backplane to prevent side
movements of the equipment on the DIN-rail. Refer to the
Emerson FB3000 RTU Instruction Manual
(D301851X012)
for details.
CSA evaluates this equipment according to the following standards:
CAN/CSA-C22.2 No. 0-10
August 2011
General requirements
—
Canadian Electrical Code, Part
II
CAN/CSA Standard C22.2 No. 213-17
UL 121201
Non-incendive Electrical Equipment for Use in Class I
and II Division 2 and Class III Division 1 and 2 Hazardous
Locations
CAN/CSA
–
C22.2 No. 60079-7:16
Explosive atmospheres
–
Part 7: Equipment protection
by increased safety “e”
UL 60079-7:17
Explosive atmospheres
–
Part 7: Equipment protection
by increased safety “e”
CAN/CSA
–
C22.2 No. 60079-0:15
Explosive atmospheres
–
Part 0: Equipment
–
General
Requirements
UL 60079-0:13
Explosive atmospheres
–
Part 0: Equipment
–
General
Requirements
Summary of Contents for FB3000
Page 7: ...FB3000 CSA Approval Information CD9411L Issued March 11 2021 CSA 5 ...
Page 8: ......
Page 12: ......
Page 46: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 34 Installation ...
Page 68: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 56 I O Configuration and Wiring ...
Page 72: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 60 Operation ...
Page 94: ......