1592040000 XR30-60-70T EN v1.3 2020.08.26
XR30-60-70T
19/40
Min
Minutes:
0 to 59 minutes
dAY
Day of the week:
Sun to Sat
dYM
Day of the month:
1 to 31
Mon
Month:
1 to 12
YAr
Year:
00 to 99
Hd1
First day of weekend:
(Sun to SAt; nu) setting for the first day of the weekend.
Hd2
Second day of weekend:
(Sun to SAt; nu) setting for the second day of the weekend.
iLE
Energy saving cycle start time on working days:
(00h00min to 23h50min) during the Energy
Saving cycle, the set point is increased by the value in HES so that the operation set point is
SET+HES
.
dLE
Energy saving cycle duration on working days:
(00h00min to 24h00min) sets the duration of
the Energy Saving cycle on working days.
iSE
Energy saving cycle start time on weekends:
00h00min to 23h50min
dSE
Energy saving cycle duration on weekends:
00h00min to 24h00min
ddx
Daily defrost enabled:
(n; Y) to enable the
Ld1 to Ld6
defrost operations for any day of the
week.
dd1
= Sunday defrost
dd2
= Monday defrost
dd3
= Tuesday defrost
dd4
= Wednesday defrost
dd5
= Thursday defrost
dd6
= Friday defrost
dd7
= Saturday defrost
Ldx
Defrost start time:
(00h00min to 23h50min) these parameters set the beginning of the
programmable defrost cycles during any
ddx
day. Example: when
Ld2=12.4,
the second defrost
starts at 12:40 am during working days.
5.1.13 Memory storage management – E2
MAP
Current configuration:
(C-1; C-2) to change configuration used.
LdM
Restore default factory settings:
(n;Y) select Y and confirm to reload factory default values for
the configuration currently used.
rHA
Reset HACCP values:
(n; Y) select Y and confirm to reset the memorized min and MAX
temperature values (HACCP function must be enabled).
5.1.14 Serial Communication port configuration parameters - CoM
Adr
Serial address:
(1 to 247) device address for Modbus communication
bAU
Baudrate:
(9.6; 19.2; 38.4; 57.6) select the correct baudrate for serial communication
PAr
Parity control:
(no; odd; EvE) no=no parity control; odd=odd parity control; EvE=even parity
control
5.1.15 User Interface configuration parameters - Ui
SCS
User interface timeout:
(1 to 255 sec) timeout before coming back to
Home Screen
or to
Programming Menu
bS
Sound Level:
(0 to 5) select the sound level of the gestures
PSU
Password for protected level Pr2:
(000 to 999) insert a value to protect all the parameters set
on the level Pr2 from modification
5.1.16 Information, read only parameters - inF
dP1
Probe P1 value visualization
dP2
Probe P2 value visualization
dP3
Probe P3 value visualization
dP4
Probe P4 value visualization
rSE
Real regulation
Set Point
FdY
Firmware release date: day
FMt
Firmware release date: month
FYr
Firmware release date: year
rEL
Firmware release: progressive number
SUb
Firmware sub release: progressive number
Ptb
Parameter map version