Pd2
Defrost output deactivation delay:
(0 to 255 sec)
dAF Pre-defrost time:
(0 to 255 min)
od1
Automatic defrost (at the beginning of any energy saving mode):
(n; Y)
n
=function disabled;
Y
=function enabled
od2
Optimized defrost:
(n;Y)
n
= function disabled;
Y
= the controller needs a temperature probe
placed on the evaporator surface to monitor the presence of ice during any defrost phase.
dSt
Temperature sampling time during an optimized defrost (valid only if od2=yes):
(1 to 255
sec) interval used to analyze the evaporator temperature and define the defrost phase
SYd
Type of synchronized defrost:
(n; SYn; nSY) n = function disabled;
SYn
= synchronized, all
devices connected will start a defrost phase at the same time.
nSY
= de-synchronized, all devices
connected will delay the beginning of the same defrost phase.
dt1
Differential temperature for latent heating control
(0.1 to 1.0 °C) to catch the latent heating
phase during any defrost
ErS
Restart regulation after dripping time, when defrost Syd = nSY: n
= disabled;
Y
= enabled
ndE
Number of devices connected to the virtual network for random defrost (valid if Syd=rnd):
(1
to 20) number of devices connected to the same network for syncro or desyncro defrost.
5.1.5 Evaporator and condenser fan configuration parameters - FAn
FAP
Probe selection for evaporator fan:
(nP; P1; P2; P3; P4)
nP
=no probe;
Px
=probe “x”. Note:
P4
=Probe on Hot Key plug.
FSt
Evaporator fan stop temperature:
(-55 to 50°C; -67 to 122°F) setting of temperature, detected by
evaporator probe. Above this temperature value fans are always OFF.
NOTE: it works only for
the evaporator fan, NOT for the condenser fan.
HYF
Evaporator fan regulator
differential:
(0.1 to 25.5°C; 1 to 45°F) evaporator fan will stop when the
measured temperature (from FAP) is T<FSt-HYF.
FnC
Evaporator fan operating mode:
(Cn; on; CY; oY)
Cn
= runs with the compressor, duty-cycle when compressor is OFF (see
FoF
,
Fon
,
FF1
and
Fo1
parameters) and OFF during defrost
on
= continuous mode, OFF during defrost
CY
= runs with the compressor, duty-cycle when compressor is OFF (see
FoF
,
Fon
,
FF1
and
Fo1
parameters) and ON during defrost
oY
= continuous mode, ON during defrost
Fnd
Evaporator fan delay after defrost cycle:
(0 to 255 min) delay before fan activation after any
defrosts.
FCt
Differential for cyclic activation of evaporator fans:
(0 to 50°C)
FSU
Evaporator fan operating mode:
(Std; Fon; FoF)
Std
= standard mode, evaporator fan uses par
FnC
;
Fon
= evaporator Fan always on;
FoF
= evaporator fan always off.
Ft
Evaporator fan controlled during defrost:
(n; Y)
n
= evaporator fan uses par.
FnC
during any
defrost;
Y
= evaporator fan regulator is active during any defrost.
Fon
Evaporator fan ON time in normal mode (with compressor OFF):
(0 to 255 min) used when
energy saving status is not active.
FoF
Evaporator fan OFF time in normal mode (with compressor OFF):
(0 to 255 min) used when
energy saving status is not active.
Fo1
Evaporator fan ON time in energy saving mode (with compressor OFF)
(0 to 255 min) used
when energy saving status is active.
FF1
Evaporator fan OFF time in energy saving mode (with compressor OFF):
(0 to 255 min) used
when energy saving status is active.
Fd1
Evaporator fan delay:
(0 to 255 sec) delay before activating evaporator fan
Fd2
Evaporator fan delay after closing door:
(0 to 255 sec) delay before activating evaporator fan
and after closing the door
FAC
Probe selection for condenser fan:
(nP; P1; P2; P3; P4)
nP
=no probe;
Px
=probe “x”. Note:
P4
=Probe on Hot Key plug.
St2
Set Point 2 regulation (for condenser fan):
(-55 to 50°C; -67 to 122°F) setting of temperature
detected by evaporator probe. Above this value of temperature fans are always OFF.
HY2
Set Point 2 differential (for condenser fan):
(0.1 to 25.5°C; 1 to 45°F) differential for evaporator
ventilator regulator
FCC
Condenser fan operating mode:
(Cn; on; CY; oY)
Cn
= runs with the compressor and OFF during defrost
on
= continuous mode, OFF during defrost
CY
= runs with the compressor and ON during defrost
oY
= continuous mode, ON during defrost